Plan Review Notes
Plan Review Notes For Permit 08060213
Permit Number 08060213
Review Stop B
Sequence Number 1
Notes
Date Text
2008-06-30 16:56:45BUILDING PLAN REVIEW
 PERMIT: 08060213
 ADD: 1401 NORTHPOINTE PARKWAY SUITE #
 CONT: CARRICK
 TEL: (561)718-9090
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) THE INFORMATION REQUESTED BELOW WILL PROVIDE FOR AN
 ACCURATE REVIEW OF YOUR PROJECT AND CREATE LESS
 QUESTIONS IN REGARDS TO THE TYPE OF CONSTRUCTION.
 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT
 IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED E)
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 F ) NUMBER OF FLOORS
  
 3) SEE ATTACHED AREIAL, IT APPEARS THIS BUILDING COVERS
 THREE INDIVDUAL LOTS, LOT NUMBER 0251, 0252 AND 0242.
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'.A 'UNITY OF TITLE'
 SHALL BE RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A
 COPY OF THE RECORDED 'UNITY OF OF TITLE' DOCUMENT SO
 THAT FBC TABLE 601 BOUNDARY LINE REQUIREMENTS MAY BE
 DEEMED NOT APPLICABLE. FORMS ARE AVALIBLE AT CITY HALL
 5TH FLOOR ZONING DEPARTMENT.
  
 4) OFFICE 100A NORTH WALL IS THE COMMON WALL TO THE
 STAIRWELL AND EXIT PASSAGEWAY THIS WALL IS NOT
 DESIGNATED AS A RATED WALLPLEASE SEE 707.4.
  
 5)IT ROOM # 107 IF THIS ROOM IS CONSIDERED A TRUE IT
 ROOM, THEN THE WALLS WILL NEED TO BE RATED SEE NEC
 645.2, ALSO SEE ELECTRICAL COMMENTS.
  
 6)LS1 THE PLAN INDICATES A NEW EXIT LIGHT IN THE
 WAREHOUSE AT DOOR# 5 VESTIBULE, BUT THE SIGHT LINE IS
 BLOCKED FROM THE IT ROOM. SEE 1006.3.1 EXIT LIGHTS
 SHALL BE MARKED AND READILY VISIBLE FROM ANY DIRECTION
 OF EXIT ACCESS. PLEASE CORRECT OR ADJUST FIXTURES.
  
 7) LS1 PLANAS ALSO INDICATE A NEW EXIT LIGHT AT DOOR#
 14 LEAVING THE BUSSINESS OCCUPANCY IN TO THE WAREHOUSE
 OCCUPANCY, THE EXISTING BUILDING CODE TABLE 812.4.1
 HAZARD CATEGORIES INDICATES BUSINESSAND S1 OCCUPANCY
 ARE OF THE SAME HAZARD CATEGORY ALLOWING EXITING
 THROUGH THE WAREHOUSE. PLEASE PROVIDE A EGRESS PATH FOR
 THE WAREHOUSE AREA.PLANS INDICATE A FENCED IN AREA AND
 GATE TO THE EGRESS DOOR. FORTHIS DOOR TO BE USED AS A
 MEANS OF EGRESS THIS GATE CAN NOT BE
 LOCKED.1013.2.ADDITIONAL EXIT LIGHTS MAY BE REQUIRED IN
 THE WAREHOUSE AREA DUE TO RACK STORAGE.1006.3.1.
  
 8) LS1 AND A-3 BOTH INDICATE IN HALL 127 CONSIDERED A
 EXIT PASSAGEWAY A FIRE EXTINGHISHER PLEASE PROVIDE
 ADDTIONAL INFORMATION ON THE DIMENSIONS OF THIS UNIT.
 1003.3.3 HORIZONTAL PROJECTIONS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.