Notes |
Date |
Text |
2008-07-16 10:32:54 | ***DENIED*** | | | | 1) BUILDING ADDRESSING TO BE APPROVED AND FINALIZED. | | THE CORRECT ADDRESS TO BE DISPLAYED IN TITLE BLOCK OF | | EACH SHEET. | | | | 2) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE | | SAFETY SHALL COMPLY WITH NFPA 101, 2003 EDITION. PLEASE | | ADD NOTE TO PLANS. | | | | 3) THE ADDRESS ON EACH BUILDING AND LIVING UNIT SHALL | | MEET THE REQUIREMENTS PER CITY OF WEST PALM BEACH CODE | | FOR MULTIPLE RESIDENTIAL UNITS. | | | | 4) EACH LIVING UNIT IS REQUIRED TO BE PROVIDED WITH | | MINIMUM 2A-10B,C RATED FIRE EXTINGUISHER. | | | | 5) BUILDING ACCESS TO COMPLY WITH REQUIREMENTS OF NFPA | | 1, 2003 EDITION CHAPTER 18. | | | | 6) INDICATE LOCATIONS OF NEW AND OR EXISTING FIRE | | HYDRANTS. NEW INSTALLATIONS SHALL BE FULLY OPERATIONAL | | PRIOR TO, DURING AND AFTER CONSTRUCTION. | | | | 7) PLEASE PROVIDE GUARDRAIL DETAIL WITH STAIR SECTION. | | MINIMUM STRENGTH REQUIREMENTS HAVE BEEN PROVIDED ON | | PLANS. | | | | 8) HARD WIRED SMOKE ALARMS SHALL BE MINIMUM OF (3') | | FROM AC DIFFUSERS. REMOVE TERM SMOKE DETECTORS IF NOT | | APPLICABLE AND REPLACE WITH SMOKE ALARMS. | | | | 9) IN ADDITION TO THE FBC, PLEASE PROVIDE OCCUPANCY | | CLAASIFICATION FOR BUILDING AS PER NFPA 101, 2003 | | EDITION. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|