Plan Review Notes
Plan Review Notes For Permit 08060139
Permit Number 08060139
Review Stop E
Sequence Number 1
Notes
Date Text
2008-07-02 14:55:31 
  
 ** DENIED REVIEW **
  
 THE FOLLOWING IS FOR THE REVIEW OF ALL UNITS *A*,*B*
 AND*C*.
  
 1) NOTE: PLEASE KNOW BASED ON PERMIT APPLICATION AND
 PLANS IT IS UNCLEAR SHOW THESE UNITS WILL ACTUALLY BE
 APPLIED. SOME ITEMS ON PLANS LEND TO A MULTI-FAMILY
 BUILDING AS THERE ARE REFERENCES TO ONE SERVICE,
 DE-RATING OF LOADS FOR MULTIPLE UNITS AND ALL AS
 APPLIED UNDER ONE ADDRESS.
 IF THESE ARE EACH A FEE SIMPLE TOWN HOUSE WITH PROPERTY
 LINES SEPARATING UNITS THIS WILL AFFECT PLANS AND
 REVIEWS.
 IF ONE BUILDING AND DONE AS A CONDO OR MULTI-FAMILY
 BUILDING THEN THE REVIEW COMMENTS WILL ALSO BE
 DIFFERENT.
  
 ** PLEASE COORDINATE APPLICATIONS, TYPES OF BUILDINGS
 ETC. PLEASE SEE COMMENTS BELOW AS THIS WILL AFFECT HOW
 THE REVIEWS/DESIGN IS CORRECTED.
  
 2) NOTE: PLEASE SEE THE APPLIED ADDRESS FOR EACH
 LOCATION ON THE TITLE BLOCKS ON PLANS NEEDS TO BE
 ACCURATE ONCE DETERMINED.
 PLEASE BE SURE TO SEE COMMENTS FROM OTHER TRADES SUCH
 AS FIRE, BUILDING AND THE ADDRESSING REVIEWER.
 PLEASE ADJUST TITLE BLOCKS FOR CORRECT ADDRESS. THIS IS
 REQUIRED FOR ALL SHEETS AND FOR ALL TRADES WHETHER OR
 NOT COMMENT IS MADE BY OTHER REVIEWERS.
 FAC 61G1-16.004, 61G15-23.002
 FBC 106.1.1, 106.5 FOR ADDITIONAL CLARITY AND RECORD
 PLANS.
  
 3) NOTE: PLEASE BE SURE THE FOLLOWING CODE IS REFLECTED
 ON PLANS. THE STATE IS CURRENTLY UNDER THE 2002
 NFPA-72. PLEASE ADJUST.
 PLEASE ALSO KNOW CODE SECTIONS SUCH AS THE NOTE ON E
 SHEETS WHICH REFERENCE SMOKE DETECTION DEVICES PER
 CHAPTER 8 ARE NO LONGER CORRECT AS THE CHAPTER UNDER
 THE CURRENT NFPA-72 HAS CHANGED.
 PLEASE SEE THE FOLLOWING COMMENTS.
 ** PLEASE KEEP IN MIND APPLICATION DATE AFFECT THE
 CODES AND CODE CHANGES WILL BE COMING THIS YEAR IN THE
 STATE OF FLORIDA.
 FS 553.73
 FBC 106.1.1, 106.5
  
 4) NOTE: PLEASE SEE NFPA-72 DEFINITIONS AS THE PLANS
 STATE THERE WILL BE SMOKE DETECTORS INSTALLED HOWEVER
 NO FIRE ALARM PANEL, HORN ETC ARE SHOWN.
 PLEASE KNOW THAT *SMOKE DETECTORS* ARE DEVICES WHICH
 ONLY *DETECT* AND DO NOT SOUND AN ALARM. SMOKE ALARMS
 ARE DEVICES WHICH DETECT AND SOUND. PLEASE VERIFY WHICH
 DEVICES ARE ACTUALLY GOING TO BE INSTALLED.
 IF THESE ARE GOING TO INDEED BE SMOKE ALARMS, PLEASE BE
 SURE TO ADJUST ALL NOTES ON PLANS WHICH INDICATE SMOKE
 DETECTORS.
 PLEASE SEE NFPA72 11.5.1.1, 11.8.3
  
 5) NOTE: PLANS MISSING REQUIRED LIGHT FIXTURE OF SOME
 SORT ON UNITS A AND B AT THE COVERED PATIO.
 PLEASE ALSO SEE THE GREAT ROOMS IN ALL THREE UNITS WILL
 REQUIRE A LIGHT FIXTURE OF SOME SORT ON THE J-BOXES
 SHOWN OR HALF SWITCHED RECEPTACLES IN SAID ROOM.
 PLEASE ALSO SEE MISSING LIGHT FIXTURE OF SOME SORT
 INSIDE UNIT *A* LAUNDRY ROOM.
 210.70
 LS101 7.8
  
 6) NOTE: PLEASE SEE THE SERVICE CALCULATIONS INDICATE A
 600AMP MAIN YET PLANS DO NOT CONTAIN ANY OTHER
 INFORMATION ON THE INDICATED SERVICE.
 230.70, 215.5, 230.76, 230.72, 230.79 ETC
  
 7) NOTE: PLEASE SEE LOAD CALCULATIONS INDICATE
 DE-RATING FOR 8 UNITS HOWEVER THE BUILDING DOES NOT
 CONTAIN 8 UNITS.
 PLEASE SEE OTHER COMMENTS LIKE #1 AND #6 AS THE LOAD
 CALCULATIONS INFORMATION ALONG WITH SERVICE DOES NOT
 COORDINATE.
 PLEASE SEE NEC 220 WHEN ACTUAL FINAL SERVICE IS
 DETERMINED.
 PLEASE COORDINATE ALL PLANS, RISER, EQUIPMENT AND LOAD
 CALCULATIONS.
 FBC 106.1.1, 106.1.2 FOR CLARITY AND ADDITIONAL
 INFORMATION.
  
 8) NOTE: PLANS INDICATE A MAIN DISCONNECT OUTSIDE OF
 EACH UNIT HOWEVER THE RISER SUBMITTED IS MISSING THE
 MAIN DISCONNECT.
 230.70, 230.71, 230.76 230.79 ETC
  
 9) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR AFTER THE FIRST MEANS OF DISCONNECT PER
 250.122, 250.24, 250.110 ETC IF MAIN IS OUTSIDE AS
 SHOWN.
  
 10) NOTE: PLEASE BE SURE TO INDICATE THE REQUIRED
 *FOOTER STEEL* AS PART OF THE GROUND ELECTRODE SYSTEM.
 THE RISER SHOWS BUILDING STEEL HOWEVER MANY TIMES AND
 PER DEFINITIONS BUILDING STEEL IS NOT FOOTER STEEL.
 PLEASE ALSO CLARIFY COLD WATER SYSTEMS IN BUILDING. IF
 METALLIC, THEN PLEASE INCLUDE ON THE RISER.
 250.50
  
 11) NOTE: PLEASE SEE 210.52B1 FOR CIRCUITING OF DINING
 ROOMS/AREAS AND OTHER AREAS OF THE LIKE.
 PLEASE SEE UNIT *A* AS THE AREA OFF KITCHEN WHICH
 APPEARS AS BREAKFAST/BAR AREA DOES FALL UNDER THE AREAS
 LISTED IN 210.52B1.
 PLEASE ADJUST PLANS AND ANY CALCULATIONS ACCORDINGLY TO
 210.11C1, 220.52
  
 12) NOTE: PLEASE SEE UNIT *A* WHICH SHOWS THE WASHER
 CIRCUITED ON WITH LIGHTS AND GARAGE RECEPTACLES WHICH
 IS NOT PERMITTED.
 PLEASE SEE 210.11C2, 220.52B
  
 13) NOTE: PLEASE SEE ALL WATER HEATER LOCATIONS PER
 422.30, 422.31 REQUIRE DISCONNECTING MEANS. A
 RECEPTACLE IS NOT PERMITTED AS SHOWN ON PLANS. THIS
 CHANGED MANY CODE CYCLES AGO IN WHICH A CORD AND PLUG
 IS NOT PERMITTED ON WATER HEATERS.
 PLEASE ADJUST PLANS FOR ALL UNITS.
  
 14) NOTE: PLEASE SEE 422.13 AS WATER HEATERS ARE NOW
 CONSIDERED A CONTINUOUS LOAD UNDER THE 2005 NEC WHICH
 REQUIRES LOADS TO BE FIGURED AT 125%.
  
 15) NOTE: PLEASE KNOW ANY ITEMS WHICH ARE SHOWN ON
 PANELS OR PLANS AS *OPTIONAL* WILL BE REQUIRED TO BE
 REVISED ON EACH AND EVERY UNIT BEFORE ROUGH ELECTRICAL
 INSPECTION ON WHETHER OR NOT THAT UNIT WILL ACTUALLY
 RECEIVE THAT OPTION.
 ** THIS IS NOTED FOR INFORMATION AT THIS TIME AS THIS
 MAY HELP WITH THE DECISION OF EACH UNIT BEFORE
 APPLICATION IS MADE.
 NEC 408.4, 310.16, 220 ETC
 FBC 106.1.1, 106.5 FOR CLARITY AND RECORD PLANS
 COORDINATION.
  
 16) NOTE: PLEASE SEE KITCHEN WALL IN UNIT *B* WHICH IS
 MISSING WALL RECEPTACLE PER 210.52
  
 17) NOTE: PLEASE INDICATEAIC RATINGS FOR ALL SERVICE
 EQUIPMENT.110.9
 PLEASE COMPLETE INFORMATION ON ELECTRICAL PANELS.
 INFORMATION ON PANELS ARE VERY VAGUE AT THIS TIME.
 110.9, 110.3, 90.7
 FBC 106.1.1, 106.1.2 FOR CLARITY AND ADDITIONAL
 INFORMATION.
  
 18) NOTE: IT IS IMPORTANT TO UNDERSTAND COMPLETION OF
 THE BUILDING NEEDS TO TAKE PLACE FOR WALLS ETC ON
 ENERGYCALCULATIONS. PLEASE SEE NOTES FROM OTHER
 TRADES AS THIS WILL AFFECT THE ENTIRE APPLICATION
 PROCESS.
 ** IT IS ALSO IMPORTANT TO UNDERSTAND AS THE RISER,
 PLANS, CALCULATIONS ETC FOR ACTUAL TYPE OF BUILDING IS
 NOT CLEAR AND THERE IS INFORMATION NOT YET SUBMITTED OR
 SHOWN IN DESIGN FOR REVIEW THERE MAY VERY WELL BE NEW
 COMMENTS ON THE FOLLOWING REVIEW. THERE MAY BE SOME
 COMMENTS WHICH COULD NOT POSSIBLY BE MADE AT THIS
 TIME.
  
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]