Date |
Text |
2008-07-28 07:55:04 | 2004 FBC W/2007 REVISIONS |
| 6 UNIT TOWN HOUSE |
| |
| DENIED BY BUILDING |
| |
| 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| BE REQUIRED. |
| |
| 2) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 3)FBC R401.4AREA OF QUESTIONABLE |
| SOIL.SUBMIT TWO COPIES OF A SIGNED AND SEALED |
| GEOTECHNICAL REPORT |
| TO VERIFY THE SAFE BEARING CAPACITY OF |
| THE SOIL. |
| |
| 4) SUBMIT TWO COPIES OF SIGNED AND SEALED TRUSS |
| DRAWINGS AND TRUSS LAYOUT DRAWINGS, THAT HAVE BEEN |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD FOR THE PROJECT. R802.1.6 |
| |
| 5) SPECIFY CARBON MONOXIDE DETECTORS ON THE PLANS AS |
| REQUIRED BY DCA RULE 9B-3.0472. |
| |
| 6) ON SHEET A1 UNDER THE GARAGE NOTES PLEASE REVISE TO |
| SPECIFY THE APPLICABLE SECTIONS OF THE FBC RESIDENTIAL |
| CODE. SEE R309.1, R 309.1.1 AND R309.2. |
| |
| 7) PLEASE PROVIDE TWO SETS OF PLANS AND DOCUMENTS AS |
| REQUIRED BY FBC 106.1* CITY AMENDMENTS. |
| |
| 8) SUBMIT TWO COPIES OF A SITE PLAN SPECIFYING THE |
| SEPARATION DISTANCES BETWEEN BUILDINGS AS WELL AS |
| DISTANCES TO PROPERTY LINES. FBC R 302.1. |
| |
| 9) FOR THE WATER HEATER ENCLOSURE UNDER THE STAIRS, |
| SHOW COMPLIANCE WITH R311.2.2 UNDER STAIR PROTECTION. |
| ENCLOSED ACCESSIBLE SPACE UNDER STAIRS SHALL HAVE |
| WALLS, UNDER STAIR SURFACE AND ANY SOFFITS PROTECTED ON |
| THE ENCLOSED SIDE WITH 1/2-INCH (12.7 MM) GYPSUM |
| BOARD. |
| |
| 10) SHOW COMPLIANCE WITH R602.1.2 FOR FIREBLOCKING OF |
| THE CONCEALED SPACE BETWEEN STAIR STRINGERS AT THE TOP |
| AND BOTTOM OF THE RUN. |
| |
| 11) WINDOWS A-D IN THE BATHROOMS ARE REQUIRED TO BE |
| SAFETY GLAZING IF THEY ARE LESS THAN 60" ABOVE THE |
| FLOOR OR WALKING SURFACE. SEE FBC R308.4. (UNIT A) |
| |
| 12) ON SHEET S2, MARK F IN THE ROOF ANCHOR SCHEDULE |
| LISTS THE MAXIMUM DESIGN UPLIFT AS 2000 LBS. AND THE |
| ALLOWABLE UPLIFT LOAD FOR THE ANCHOR IS 1215 LBS. |
| PLEASE CORRECT. FBC R802.1.6.5 |
| |
| 13) FBC R803.2.3.1 REQUIRES ROOF SHEATHING TO BE |
| FASTENED WITH 8D RING SHANK NAILS AND 10D COMMON NAILS |
| ARE SPECIFIED. PLEASE REVISE. |
| |
| 14) ON SHEET S4 A HEAD WALL FIRESTOPPING DETAIL FROM 3M |
| HW-D-0075 MODIFIED BY JUDGEMENT # 518786 IS SPECIFIED. |
| PLEASE SUBMIT TWO SIGNED AND SEALED COPIES OF THE |
| JUDGEMENT FROM THE MANUFACTURER'S ENGINEER. |
| |
| 15) PROVIDE CALCULATIONS FOR ROOF VENTILATION SHOWING |
| COMPLIANCE WITH R806.2 MINIMUM AREA. |
| THE TOTAL NET FREE VENTILATING AREA SHALL NOT BE LESS |
| THAN 1 TO 150 OF THE AREA OF THE SPACE VENTILATED |
| EXCEPT THAT THE TOTAL AREA IS PERMITTED TO BE REDUCED |
| TO 1 TO 300, PROVIDED AT LEAST 50 PERCENT AND NOT MORE |
| THAN 80 PERCENT OF THE REQUIRED VENTILATING AREA IS |
| PROVIDED BY VENTILATORS LOCATED IN THE UPPER PORTION OF |
| THE SPACE TO BE VENTILATED AT LEAST 3 FEET (914 MM) |
| ABOVE EAVE OR CORNICE VENTS WITH THE BALANCE OF THE |
| REQUIRED VENTILATION PROVIDED BY EAVE OR CORNICE VENTS. |
| AS AN ALTERNATIVE, THE NET FREE CROSS-VENTILATION AREA |
| MAY BE REDUCED TO 1 TO 300 WHEN A VAPOR BARRIER HAVING |
| A TRANSMISSION RATE NOT EXCEEDING 1 PERM IS INSTALLED |
| ON THE WARM SIDE OF THE CEILING. |
| |
| 16) SUBMIT TWO COPIES OF THE ENERGY CALCULATION FORMS |
| SIGNED BY THE OWNER/AGENT. USE WORST CASE CALCULATIONS |
| OR THEY WILL NEED TO BE DIFFERENT DEPENDING ON THE |
| ORIENTATION OF THE BUILDING. ALSO MAKE CORRECTIONS |
| NOTED IN COMMENTS FROM OTHER TRADES. FBC CHAPTER 13. |
| |
| 17) PLEASE COMPLY WITH FBC 106.3* CITY AMENDMENTS |
| PRODUCT APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY |
| DCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN |
| WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 18) SUBMIT TWO COPIES OF PRODUCT APPROVALS AS REQUIRED |
| BY DCA RULE 9B-72 FOR THE FOLLOWING ITEMS: WINDOW |
| MULLIONS, CONCRETE LINTELS, SIMPSON AND USP |
| CONNECTORS. |
| |
| 19) SUBMIT TWO COPIES OF A KEY PLAN AND INSTALLATION |
| SCHEDULE FOR THE STORM PANELS. SPECIFY THE CONNECTION |
| TYPE, EDGE DISTANCE, SPAN, ANCHOR TYPE AND ANCHOR |
| SPACING. FBC R 301.2.1.2. SEE ATTACHED. |
| |
| 20) THE NOA THAT WAS SUBMITTED FOR THE LAWSON FIXED |
| WINDOW EXPIRED ON MAY 08, 2008. SUBMIT CURRENT NOA NO. |
| 08-0409.03. |
| |
| 21) THE 1/8" ANNEALED GLASS LISTED IN THE LAWSON HS |
| WINDOW NOA DOES NOT HAVE ADEQUATE DESIGN PRESSURES FOR |
| THE 6' X 4' XO OR OX HS WINDOWS. HOWEVER, THE OTHERS DO |
| HAVE ADEQUATE DESIGN PRESSURES. PLEASE SPECIFY THE |
| GLAZING OPTION THAT WILL BE USED IN THE NOA. R301.2.1 |
| |
| 22) THE NOA FOR THE AMARR GARAGE DOOR EXPIRES ON |
| SEPTEMBER 4, 2008. ANY PERMITS APPLIED FOR AFTER THAT |
| DATE WILL REQUIRE A CURRENT NOA. DCA RULE 9B-72 |
| |
| 23) THE VALUE OF THE STRUCTURE HAS BEEN DETERMINED TO |
| BE $156,438.00 USING ICC BUILDING VALUATION DATA. |
| ADDITIONAL FEES OF $232.06ARE DUE. |
| |
| 24) AN ADDRESS IS REQUIRED TO BE ASSIGNED TO THE UNIT |
| BY THE CITY BEFORE A PERMIT CAN BE ISSUED. PLEASE |
| CONTACT LACRAMIOARA URSU @ 561-822-1239. |
| |
| NOTE: THE PLANS SPECIFY EXPOSURE CATEGORY B WHICH IS |
| CORRECT FOR MOST OF THE BUILDINGS. HOWEVER,THE 8 UNIT |
| BUILDINGS NUMBERS 1, 4, 9 AND 14 ARE EXPOSURE CATEGORY |
| C. SEE FBC R 301.2.1.4. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| [email protected] |