Plan Review Notes
Plan Review Notes For Permit 08060116
Permit Number 08060116
Review Stop E
Sequence Number 4
Notes
Date Text
2009-06-15 14:37:50 
  
  
  
 ** DENIED REVISIONS *
  
 1) NOTE: E-3 SUBMITTED AS REVISED YET THERE ARE NO
 REVISIONS FROM THE RECORD SET OF PLANS. THE LAST
 REVISED SHEET NOTED IN THE TITLE BLOCK IS FROM
 7/13/2008. THE NEW SHEET E-3 SUBMITTED HAS THE SAME
 REVISION DATED 7/13/2008.
 ** PLEASE ONLY SUBMIT SHEETS WHICH ARE INDEED BEING
 REVISED.
  
 2) NOTE: PLEASE SEE E-1. NOTE ON THE SCOPE OF WORK HAS
 BEEN REVISED WITH THE REV #2, HOWEVER IT IS UNCLEAR
 WHAT THE REVISION IS? THE SENTENCE IN THIS NOTE STATES:
 * CONNECT NEW TANKS TO*. WHAT ARE THE NEW TANKS BEING
 CONNECTED TO? PLEASE COMPLETE NOTES FOR REVIEW AND
 COORDINATION FOR CODE COMPLIANCE.
 NEC 514 AND FBC 106.5, 106.1.1 FOR CLARITY AND
 COORDINATION OF PLANS.
  
 3) NOTE: PLEASE COORDINATE PLANS. THE PLANS FOR E-2 NOW
 INDICATE THAT THE EXISTING PANEL G WHICH WAS BEING
 REPLACED IS NOW GOING TO REMAIN. HOWEVER THE RISER
 STILL INDICATES THE PANEL G AS A 20 CIRCUIT MLO YET THE
 REVISED PANEL HAS NOW GONE FROM THE QO 24 ON RECORD
 PLANS TO A QO16.
 WHICH ONE WILL IT BE? THE NEW REVISED PANEL SCHEDULE
 SHOWS 16, BUT THIS IS IN CONFLICT WITH THE RISER NOTES.
  
 4) NOTE: PLEASE PROVIDE MORE INFORMATION ON STP RELAYS.
 THE RISER HAS NOW BEEN REVISED TO REMOVE ALL STP RELAYS
 HOWEVER THE PANEL SCHEDULE STILL LISTS FOUR. THE ONLY
 ONE REVISED WAS FOR *FUTURE DIESEL STP*.
 PLEASE COORDINATE.
 NEC 514, AND FBC 106.5, 106.1.1 FOR CLARITY AND
 COORDINATION OF RECORD PLANS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  