2008-06-30 14:18:57 | BUILDING PLAN REVIEW |
| PERMIT: 08060116 |
| ADD: 1541 BELVEDERE RD |
| CONT: GUARIDIAN FUELING TECH |
| TEL: (904)680--0860 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1A) INFORMATIONAL FL S S 713.13NOTICE OF |
| COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. |
| NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS |
| AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| INSPECTION. |
| |
| 1B)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS. |
| |
| 2) PLANS FAIL TO INDICATE WIND LOAD INFORMATION AND HOW |
| THE NEW PUMPS ARE GOING TO BE ATTACHED TO RESIST THE |
| MOMENT OF OVERTURNING. |
| 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE |
| BUILDING: |
| 1.BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| (KM/HR). |
| 2.WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3. |
| WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| DIRECTION SHALL BE INDICATED. |
| 4.THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| 5.COMPONENTS AND CLADDING. THE DESIGN WIND |
| PRESSURES IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE |
| SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS |
| NOT SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN |
| PROFESSIONAL. |
| 1609. |
| 1609.1.3 ANCHORAGE TO RESIST THE MOMENT OF |
| OVER-TURNING, UPLIFT AND SLIPPAGE. |
| |
| 3) SHEET G-6 PLEASE INDICATE COMPLIANCE WITH REACH |
| RANGESFOR THE DESPENSER DETAIL. 11-4.27.3- 11-4.27.4. |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |