2008-06-19 11:40:37****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1.SEE ATTACHED IMPLEMENTATION STANDARD, ITEM 13.USE
 OF REMOVABLE IMPACT PROTECTION ON COMMERCIAL BUILDINGS
 REQUIRES APPROVAL BY THE BUILDING OFFICIAL.PLEASE
 PROVIDE A PRE STORM PREPARATION PLAN WITH ALL
 INFORMATION REQUIRED.A PRELIMINARY REVIEW MAY BE DONE
 BY EMAIL PRIOR TO RESUBMITTAL.THE CONTRACTOR IS
 ENCOURAGED TO HAVE THE PRE STORM PREPARATION PLAN
 APPROVED PRIOR TO RESUBMITTAL.
  
 A PRESTORM PREPARATION PLAN WAS SUBMITTED.PLEASE
 REVISE THE PLAN AS FOLLOWS:
  
 THIS MUST BE SIGNED BY THE OWNER AS THE OWNER IS
 AGREEING TO HAVE THE SHUTTERS INSTALLED WITHIN A
 SPECIFIED TIME FRAME.
  
 THE PLAN IS TO INCLUDE TIME FRAME; WHEN THE SHUTTERS
 WILL BE INSTALLED.PLEASE SEE THE POLICY WHICH WAS
 INCLUDED IN THE FIRST DENIED PACKAGE; ALSO AVAILABLE IN
 OUR LOBBY.
  
 HOW WILL THE ROOF BE ACCESSED?WHERE IS THE EQUIPMENT,
 IF ANY IS REQUIRED, TO BE STORED?
  
  
  