Plan Review Notes
Plan Review Notes For Permit 08060051
Permit Number 08060051
Review Stop M
Sequence Number 1
Notes
Date Text
2008-06-26 08:20:45PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SHOW COMPLIANCE WITH NFPA 37, 6.3.2.4 FUEL
 TANKS WITHIN STRUCTURES SHALL BE PROVIDED WITH SPILL
 CONTAINMENT CONSISTING OF EITHER A WALL, A CURB, OR A
 DIKE HAVING A CAPACITY AT LEAST EQUAL TO THAT OF THE
 LARGEST SURROUNDED TANK.
  
 2) PLEASE SHOW ON PLANS OR STATE IF THERE ARE ANY OTHER
 BUILDINGS, BUILDING OPENINGS, PROPERTY LINES, OR
 WALKWAYS WITH IN 10 FEET OF THE GENERATOR EXHAUST
 OUTLET, PER NFPA 37.
  
 3) PLAN M-1 SHOWS A 72"X48" LOUVER IS TO BE INSTALLED.
 PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR LOUVER,
 SEE FS 553.842(1) AND FAC RULE 9B-72, 9B-72.005, AND
 FAC 9B-72.010(31)(C).
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 *** PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND
 SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B.
 AMEND. 106.3.
  