Plan Review Notes
Plan Review Notes For Permit 08060051
Permit Number 08060051
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-07-03 10:12:17***DENIED***
  
 1) TITLE BLOCK SHOWS AN ADDRESS OF 215 OLIVE AVE. AND
 PERMIT APPLICATION INDICATES 300 N. DIXIE HIGHWAY.
 PLEASE CORRELATE AND IF ADDRESS IS ON OLIVE AVE,
 INDICATE NORTH OR SOUTH.
  
 2) INDICATE ADOPTED EDITIONS UNDER CODES AND STANDARDS.
 IN ADDITION, NFPA 110 STANDARD FOR EMERGENCY AND
 STANDBY POWER SYSTEMS SHALL BE REFERENCED.
  
 3) PROVIDE MANUFACTURER SPECIFICATION SHEETS FOR
 GENERATOR AND ASSOCIATED EQUIPMENT.
  
 4) ILLUSTRATE BUILDING OPENINGS IN RELATION TO THE
 EXHAUST TERMINUS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756