Plan Review Notes For Permit 08060051 |
Permit Number |
08060051 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-07-02 13:04:13 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | NEC, NFPA-72 2002, NFPA-101 2003, NFPA-37, 2004 FBC | | CHAPTER 1 AS AMENDED AND FOUND NONCOMPLIANT WITH THE | | FOLLOWING: | | | | SHEET E-4: | | | | 1} PROVIDE PANEL SCHEDULES FOR "EML" AND "EMP". | | | | 2} CIRCUIT #3 IN PANEL "EDP" INCORRECTLY LISTS PANEL | | "EMP" AS A FEED, IT FEEDS PANEL "EML" ON THE RISER | | DIAGRAM. | | | | 3} TRANSFORMER "PEG" MUST HAVE PRIMARY AND SECONDARY | | OVERCURRENT PROTECTION PER 450.3(B). | | | | 4} INDICATE THE INPUT AND OUTPUT VOLTAGES FOR | | TRANSFORMER "PEG". | | | | 5} INDICATE THE EMERGENCY FEED FOR PANEL "EGP", | | TRANSFORMER "T-2" AND PANEL "EGR". HOW ARE THE GARAGE | | EMERGENCY LIGHTS BEING FED? | | | | 6} VERIFY THAT XFMR "PEG" AT 15KVA WILL FEED THE 28KVA | | LOAD ON "EMP". | | | | 7} PER NFPA-37.4.1.2.3ENGINE ROOMS LOCATED WITHIN | | STRUCTURES SHALL HAVE INTERIOR WALLS, FLOORS, AND | | CEILINGS OF AT LEAST 1-HOUR FIRE RESISTANCE RATING. | | SHEET E-3 INDICATES A METALLIC FENCE ENCLOSING THE | | GENERATOR. | | | | PROVIDE A WRITTEN RESPONSE, REMOVE OLD AND VOIDED | | SHEETS AND PROVIDE ONE COPY OF THE OLD PLANS WHEN | | RESUBMITTING. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|