 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, NFPA-37, 2004 FBC
 CHAPTER 1 AS AMENDED AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 SHEET E-4:
  
 1} PROVIDE PANEL SCHEDULES FOR "EML" AND "EMP".
  
 2} CIRCUIT #3 IN PANEL "EDP" INCORRECTLY LISTS PANEL
 "EMP" AS A FEED, IT FEEDS PANEL "EML" ON THE RISER
 DIAGRAM.
  
 3} TRANSFORMER "PEG" MUST HAVE PRIMARY AND SECONDARY
 OVERCURRENT PROTECTION PER 450.3(B).
  
 4} INDICATE THE INPUT AND OUTPUT VOLTAGES FOR
 TRANSFORMER "PEG".
  
 5} INDICATE THE EMERGENCY FEED FOR PANEL "EGP",
 TRANSFORMER "T-2" AND PANEL "EGR". HOW ARE THE GARAGE
 EMERGENCY LIGHTS BEING FED?
  
 6} VERIFY THAT XFMR "PEG" AT 15KVA WILL FEED THE 28KVA
 LOAD ON "EMP".
  
 7} PER NFPA-37.4.1.2.3ENGINE ROOMS LOCATED WITHIN
 STRUCTURES SHALL HAVE INTERIOR WALLS, FLOORS, AND
 CEILINGS OF AT LEAST 1-HOUR FIRE RESISTANCE RATING.
 SHEET E-3 INDICATES A METALLIC FENCE ENCLOSING THE
 GENERATOR.
  
 PROVIDE A WRITTEN RESPONSE, REMOVE OLD AND VOIDED
 SHEETS AND PROVIDE ONE COPY OF THE OLD PLANS WHEN
 RESUBMITTING.
  