Plan Review Notes For Permit 08060026 |
Permit Number |
08060026 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-06-11 07:25:45 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 | | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN | | THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE | | INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS | | DESIGNED. | | | | 2} NO ELECTRICAL PLANS HAVE BEENSUBMITTED FOR REVIEW. | | PLANS INDICATING THE SCOPE OF WORK MUST BE SUBMITTED | | WITH THE APPLICATION. 106.1 FBC AS AMENDED. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | |
|