Date Text
2008-07-28 17:41:31AMY STELLY
 URBAN DESIGN
 822-1440
  
 1. PLEASE SHOW THE LOCATION OF ALL WINDOWS SO THAT
 ADEQUATE VENTILLATIONAND LIGHTING CAN BE VERIFIED.
  
 ARTICLE IV, SEC 18-95
 (B)EVERY HABITABLE ROOM SHALL HAVE AT LEAST ONE
 WINDOW OR SKYLIGHT FACING DIRECTLY TO THE OUTSIDE OR
 OTHER MEANS OF LIGHTING WHICH IS APPROVED AS ADEQUATE
 BY THE INSPECTOR. THE MINIMUM TOTAL WINDOW AREA FOR
 EVERY HABITABLE ROOM SHALL BE TEN PERCENT OF THE TOTAL
 FLOOR AREA OF SUCH ROOM; IF THE ONLY WINDOW IN A ROOM
 IS THE SKYLIGHT TYPE, THE MINIMUM TOTAL WINDOW AREA
 SHALL BE 15 PERCENT OF TOTAL FLOOR AREA OF SUCH ROOM,
 EXCEPT WHERE OTHER MEANS OF ARTIFICIAL LIGHTING ARE
 APPROVED.
  
 ARTICLE IV, SEC. 18-96.MINIMUM STANDARDS FOR
 VENTILATION.
 (A)EVERY HABITABLE ROOM SHALL HAVE AT LEAST ONE
 WINDOW OR SKYLIGHT OPENING DIRECTLY TO THE OUTDOORS
 WHICH CAN EASILY BE OPENED, OR SUCH OTHER DEVICE AS
 WILL ADEQUATELY VENTILATE THE ROOM. THE MINIMUM TOTAL
 OPENABLE WINDOW AREA IN EVERY HABITABLE ROOM SHALL BE
 EQUAL TO 45 PERCENT OF THE MINIMUM TOTAL WINDOW AREA
 REQUIRED IN SUBSECTION 18-95(B), EXCEPT WHERE THERE IS
 SUPPLIED SOME OTHER DEVICE AFFORDING ADEQUATE
 VENTILATION AND APPROVED BY THE BUILDING OFFICIAL. (B)
 WHEN WALLS OR OTHER PORTIONS OF STRUCTURES FACE A
 WINDOW AND ARE LOCATED LESS THAN THREE FEET FROM THE
 WINDOW AND EXTEND TO A LEVEL ABOVE THAT OF THE CEILING
 OF THE ROOM SO AS TO BE A LIGHT OBSTRUCTION FEATURE,
 SUCH WINDOW SHALL NOT BE INCLUDED AS CONTRIBUTING TO
 THE REQUIRED MINIMUM TOTAL WINDOW AREA.
 (C)EVERY BATHROOM SHALL HAVE VENTILATION EQUAL TO
 FOUR SQUARE FEET OR SUCH OTHER DEVICE AS WILL
 ADEQUATELY VENTILATE THE ROOM AND WHICH IS APPROVED BY
 THE BUILDING OFFICIAL.
  
 2. PLEASE SUBMIT A SITE PLAN SHOWING PARKING AND
 DUMPSTER LOCATION.
  
 3. THERE ARE ROOMING UNITS ON THE PLAN THAT ARE LESS
 THAN 70 SQUARE FEET. PLEASE CONSIDER ENLARGING THE
 UNITS.
  
  
  
  