Plan Review Notes
Plan Review Notes For Permit 08060012
Permit Number 08060012
Review Stop P
Sequence Number 2
Notes
Date Text
2008-07-16 16:17:47PLUMBING PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW
 COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW
 COMMENTS.
 NOTE: THERE WERE NO COMMENT RESPONSES FROM THE
 DESIGNER.
  
 1. A} & B} "OK" COMMENTS ADDRESSED.
  
 2. A} & B} "OK" COMMENT ADDRESSED.
  
 3. PROVIDE DETAILS OF FIRE STOPPING OF NEW PROPOSED
 PVC SANITARY PLUMBING PIPIES THROUGH FLOORS COMPLIANT
 WITH FBC-2004 BUILDING SECTION 717 CONCEALED SPACES
 WITH UL LISTINGS.
  
 **NOTE: NO COMMENT RESPONSE FROM THE DESIGNER AND
 COMMENT WAS NOT ADDRESSED.
  
 4. CLEARLY IDENTIFY ALL PLUMBING FIXTURES ON THE
 PROPOSED BATHROOM FLOOR PLANS. THE SHOWER ON THE FLOOR
 PLAN LOOKS LIKE A BATHTUB. PER FBC-2004 PLUMBING
 SECTION 401.1 SCOPE.
  
 **NOTE: NO COMMENT RESPONSE FROM THE DESIGNER AND THE
 COMMENT WAS NOT COMPLETELY ADDRESSED. SOME FIXTURES ARE
 STILL NOT CLEARLY IDENTIFIED.
  
 5. PROVIDE THE FOLLOWING INFORMATION FOR THE PROPOSED
 1ST FLOOR ADA BATHROOM COMPLIANT WITH FBC-2004 CHAPTER
 11 FLORIDA ACCESSIBILITY CODE.
  
 **NOTE: NO COMMENT RESPONSE FROM THE DESIGNER AND THE
 COMMENT WAS PARTIALLY ADDRESSED. BELOW ARE THE ITEMS
 THAT STILL NEED TO BE ADDRESSED TO MEET ADA
 COMPLIANCE.
  
 **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
  
 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28.**NOTE:
 COMMENT NOT ADDRESSED. CLEARLY INDICATE THE CLEAR FLOOR
 SPACE ON THE PROPOSED ADA COMPLIANT 1ST FLOOR BATHROOM
 FLOOR PLAN.
  
 11-4.16.3 HEIGHT. 17" TO 19".
 **NOTE: COMMENT NOT ADDRESSED ON WATER CLOSET ADA
 DETAILS.
  
 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44"
 HIGH.
 **NOTE: COMMENT NOT ADDRESSED ON WATER CLOSET ADA
 DETAILS.
  
 11-4.16.6 DISPENSERS. SEE FIGURE 29(B).
 **NOTE: COMMENT NOT ADDRESSED ON WATER CLOSET ADA
 DETAILS.
  
 **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL
 REQUIRED WITH THE FOLLOWING INFORMATION)
  
 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE
 32)
 **NOTE: COMMENT NOT ADDRESSED. CLEARLY INDICATE THE
 CLEAR FLOOR SPACE ON THE PREPOSED ADA COMPLIANT 1ST
 FLOOR BATHROOM FLOOR PLAN.
  
 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 **NOTE: COMMENT NOT ADDRESSED ON LAVATORY & MIRROR ADA
 DETAIL.
  
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
 **NOTE: COMMENT NOT ADDRESSED ON LAVATORY & MIRROR ADA
 DETAIL.
  
 ** 11-4.20 BATHTUBS (ELAVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION)
  
 11-4.20.2 CLEARFLOOR SPACE. (SEE FIGURE 33)**NOTE:
 COMMENT NOT ADDRESSED. CLEARLY INDICATE THE CLEAR FLOOR
 SPACE ON THE PROPOSED ADA COMPLIANT 1ST FLOOR BATHROOM
 FLOOR PLAN.
  
 11-4.20.3 SEAT. REQUIRED. (SEE FIGURE 33 & 34)**NOTE:
 COMMENT NOT ADDRESSED ON BATHTUB ADA DETAIL. CLEARLY
 INDICATE THE SEAT ON THE DETAIL.
  
 6. "OK" COMMENT ADDRESSED.
  
 **THE FOLLOWING ARE NEW ITEMS THAT NEED TO BE
 ADDRESSED DUE TO THE RESUBMITTED PLANS WITH DESIGN
 CHANGES**
  
 7. 1ST AND 2ND FLOOR PLAN PLUMBING ISOMETRICS: PLEASE
 CLEARLY INDICATE THE VENT TERMINATION FROM THE PROPOSED
 1ST FLOOR BATHROOM. PLAN INDICATES "TO 2ND FLOOR",
 HOWEVER THERE IS NO CONTINUATION OF THIS VENT INDICATED
 ON THE 2ND FLOOR ISOMETRIC. PER FBC- PLUMBING SECTION
 901.1 SCOPE AND SECTION 903.3 VENT TERMINATION.
  
 8. DUE TO THE FACT THAT THIS IS A COMMERICIAL R-2
 BUILDING PLEASE PROVIDE THE FOLLOWING. PER FBC-2004
 CHAPTER 1, SECTION 106.3.5.1.3, PLUMBING
 (3)(5)(8)(10)(13): AN ISOMETRIC POTABLE WATER RISER
 DIAGRAM IS REQUIRED FOR THE PROPOSED WORK FOR BOTH THE
 HOT AND COLD WATER INDICATING THE PIPE SIZES, VALVE
 LOCATIONS, LOCATION OF THE WATER SUPPLY LINE WITH
 BACKFLOW PREVENTER **608, THERMAL EXPANSION CONTROL FOR
 THE WATER HEATER **607.3, AND LOCATION OF THE
 WATER-HAMMER ARRESTORS WHERE QUICK CLOSING VALVES ARE
 UTILIZED (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE
 MAKERS) **604.9.
 NOTE: IF THE WATER HEATER W/THERMAL EXPANSION CONTROL
 AND THE BACKFLOW PREVENTER ARE EXISTING, PLEASE CLEARLY
 INDICATE THIS ON THE PLANS.
  
 9. THE 1ST AND 2ND FLOOR PLAN PLUMBING ISOMETRICS: THE
 LEGENDS DO NOT INDICATE WHAT A BT (BATHTUB W/SHOWER)
 TYPE FIXTURE IS. ALSO ON THE 2ND FLOOR PLAN PLUMBING
 ISOMETRIC THE BT (BATHTUB W/SHOWER) IS NOT IDENTIFIED.
 PER FBC- PLUMBING SECTIONS 401.1 AND 701.1 SCOPE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730