2008-07-31 13:35:08 | |
| BUILDING PLAN REVIEW |
| PERMIT: 08060012 |
| ADD: 1117 N. ROSEMARY AVE. |
| CONT: KDN CONSTRUCTION SERVICES |
| TEL: (561)662-1002 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 1ST |
| ACTION: DENIED |
| |
| 1)WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| **NO RESPONSE NOT ADDRESSED** INDICATE THE TYPE OF |
| BUILDING PER CHAPTER 6 AND TABLE 601 AND TABLE 503. IS |
| THERE A FIRE SPRINKLER SYSTEM IN THE BUILDING? IF SO, |
| SHOW HOW THE NEW WALLS WILL AFFECT THE LAYOUT OF THE |
| SPRINKLER HEADS. THE NEW LAYOUT MAY BE SHOWN ON THE |
| REFLECTED CEILING PLANS. 106.3.5.1.1(5) |
| 3)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE 2007 SUPPLEMENTS. |
| |
| **NO RESPONSE NOT ADDRESSED** |
| 4) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN |
| OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| THIS CODE. |
| |
| |
| **NO COMMENT NOT ADDRESSED** |
| 5)IF BOTH BATHROOMS ARE TO BE ACCESSIBLE THEY SHALL |
| MEET THE REQUIREMENTS 11-4.16, 11-4.19, 11-4.20 AND |
| 11-4.23. INDICATE THE CLEAR FLOOR SPACE ON THE |
| DRAWINGS.THE PLANS SHALL INDICATE THE TYPE OF BACKING |
| SUPPORT FOR THE GRAB RAILS. THE PROPOSED SECOND FLOOR |
| BATH ROOM IS MISSING THE LOCATION THE GRAB BARS. AS |
| STATED IN THE FIRST REVIEW THE ACCESSIBLE BATHROOMS |
| SHALL MEET THE REQUIREMENTS OF SECTIONS ABOVE. AN |
| IN-TUB SEAT SHALL BE PROVIDED PER 11-4.20.3 AND FIG 33 |
| AND 34. IF A SHOWER IS INSTALLED INSTEAD OF A TUB, SEE |
| 11-4.21. PROVIDE ELEVATION DRAWINGS SHOWING THESE |
| REQUIREMENTS. |
| |
| 6) OK |
| |
| 7)STATE WHAT TYPE OF MATERIALS WILL BE USED TO |
| CONSTRUCT THE NEW STORAGE ROOM AND INDICATE THE TYPE |
| AND QUANTITY OF MATERIALS WHICH WILL BE STORED. NOTE: |
| THE WALLS MAY REQUIRE A FIRE RATING, DEPENDING ON THE |
| STORED MATERIALS. ADDITIONAL INFORMATION IS REQUIRED. |
| 106.1.2* |
| |
| THE SCALE ON THE PLANS INDICATES 1/4" PER FOOT; |
| HOWEVER, THE DIMENSIONS INDICATED ON THE DRAWINGS DO |
| NOT CORRESPOND WITH THE ?? SCALE. INDICATE THE SIZE OF |
| THE DOORS OF THE NEW ACCESSIBLE BATHROOMS. SEE FBC |
| (EXISSTING) 605.5.1.1 |
| 8)ALL SHEETS SHALL BEAR THE PRINTED NAME AND |
| SIGNATURE OF THE PERSON TAKING RESPONSIBILITY FOR THE |
| DRAWINGS. BUILDING PLANS SHALL BE DRAWN TO A MINIMUM |
| 1/8 INCH SCALE. 106.1.3 |
| |
| **NEW** THE CLAIMED VALUATION ON THE PERMIT APPLICATION |
| IS LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| (BVD) MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| PER 108.3 FBC* |
| |
| 712.4.1.2 FLOOR PENETRATIONS FOR THE PIPES SHALL MEET |
| THE REQUIREMENTS BELOW, WHICH SHALL BE SHOWN ON THE |
| DRAWINGS. |
| THROUGH PENETRATIONS SHALL BE PROTECTED BY AN APPROVED |
| THROUGH-PENETRATION FIRE-STOP SYSTEM INSTALLED AND |
| TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A |
| MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH OF |
| WATER. THE SYSTEM SHALL HAVE AN F RATING AND A T RATING |
| OF NOT LESS THAN 1 HOUR BUT NOT LESS THAN THE REQUIRED |
| RATING OF THE FLOOR PENETRATED. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| (561)805-6726 |
| [email protected] |