Plan Review Notes
Plan Review Notes For Permit 08060012
Permit Number 08060012
Review Stop P
Sequence Number 1
Notes
Date Text
2008-06-11 14:20:48PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. 1ST FLOOR PLAN PLUMBING ISOMETRIC: PLEASE CORRECT
 THE FOLLOWING PER FBC-2004 PLUMBING THE FOLLOWING
 SECTIONS.
  
 A} PLEASE DELETE THE WATER-SEAL TRAP BEING INDICATED
 FOR THE WATER CLOSET. A WATER CLOSET HAS AN INTEGRAL
 TRAP AND ONE IS NOT REQUIRED. PER SECTION 1002.1
 FIXTURE TRAPS.
  
 B} WHY IS THERE A CLEANOUT BEING INDICATED BETWEEN THE
 WATER CLOSET AND THE SHOWER? ITS NOT REQUIRED AND
 SHOULD BE DELETED. PER SECTION 701.1 SCOPE.
  
 2. 2ND FLOOR PLAN PLUMBING ISOMETRIC: PLEASE CORRECT
 THE FOLLOWING PER FBC-2004 PLUMBING THE FOLLOWING
 SECTIONS.
  
 A} PLEASE DELETE THE WATER-SEAL TRAP BEING INDICATED
 FOR THE WATER CLOSET. A WATER CLOSET HAS AN INTEGRAL
 TRAP AND ONE IS NOT REQUIRED. PER SECTION 1002.1
 FIXTURE TRAPS.
  
 B} THE HORIZONTAL DRY VENT BEING INDICATED BETWEEN THE
 WATER CLOSET AND THE VENT STACK IS NOT ALLOWED. PLEASE
 REFERENCE THE ATTACHED ISOMETRIC EXAMPLE ATTACHED TO
 THE 2ND FLOOR ISOMETRIC SHEET THATS COMPLIANT. PER
 SECTION 905.3 VENT CONNECTION TO DRAINAGE SYSTEM.
  
 3. PROVIDE DETAILS OF FIRE STOPPING OF NEW PROPOSED
 PVC SANITARY PLUMBING PIPIES THROUGH FLOORS COMPLIANT
 WITH FBC-2004 BUILDING SECTION 717 CONCEALED SPACES
 WITH UL LISTINGS.
  
 4. CLEARLY IDENTIFY ALL PLUMBING FIXTURES ON THE
 PROPOSED BATHROOM FLOOR PLANS. THE SHOWER ON THE FLOOR
 PLAN LOOKS LIKE A BATHTUB. PER FBC-2004 PLUMBING
 SECTION 401.1 SCOPE.
  
 5. PROVIDE THE FOLLOWING INFORMATION FOR THE PROPOSED
 1ST FLOOR ADA BATHROOM COMPLIANT WITH FBC-2004 CHAPTER
 11 FLORIDA ACCESSIBILITY CODE.
  
 **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. 11-4.16.3
 HEIGHT. 17" TO 19".
 11-4.16.4 GRAB BARS. SEE FIGURE 29. GRAB BAR BEHIND W/C
 36" LONG.
 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44"
 HIGH.
 11-4.16.6 DISPENSERS. SEE FIGURE 29(B).
  
 **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL
 REQUIRED WITH THE FOLLOWING INFORMATION)
 11-4.19.2 HEIGHT AND CLEARANCES. MAXIMUM 34" TO RIM OR
 COUNTER. 29" A.F.F. TO THE BOTTOM OF THE APRON. (SEE
 FIGURE 31)
 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE
 32)
 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
 11-4.19.6 MIRRORS. 40" MAXIMUM A.F.F.
  
 ** 11-4.20 BATHTUBS (ELAVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION)
 11-4.20.2 FLOOR SPACE. (SEE FIGURE 33)
 11-4.20.3 SEAT. REQUIRED. (SEE FIGURE 33 & 34)
 11-4.20.4 GRAB BARS. REQUIRED. (SEE FIGURE 33 & 34)
 11-4.20.5 CONTROLS. (SEE FIGURE 34)
 11-4.20.6 SHOWER UNIT. SHOWER SPRAY UNIT WITH A HOSE
 MINIMUM 60" LONG USED BOTH AS A FIXED OR HAND HELD
 SHALL BE PROVIDED.
  
 **11-4.21 SHOWER STALLS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
 11-4.21.2 SIZE AND CLEARANCES. (SEE FIGURES 35(A) OR
 (B) AND FIGURES 57 (A) OR (B)
 11-4.21.3 SEAT. REQUIRED IN A 36" X 36" (17"-19" HIGH)
 11-4.21.4 GRAB BARS. REQUIRED (SEE FIGURE 37) 11-4.21.5
 CONTROLS. REQUIRED (SEE FIGURE 37) 11-4.21.7 CURBS. 36"
 X 36" MAXIMUM 1/2" CURB (NO CURB REQUIRED IN MINIMUM
 30" X 60" STALLS)
  
 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE
 SHALL BE 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR
 SPACE (PER 11-4.2.3)
  
 6. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
 NOTE: FLOOR PLAN SHEETS ARE NOT SIGNED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved