2008-06-11 08:39:13BUILDING PLAN REVIEW
 PERMIT: 08060012
 ADD: 1117 N. ROSEMARY AVE.
 CONT: KDN CONSTRUCTION SERVICES
 TEL: (561)662-1002
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 5)IF BOTH BATHROOMS ARE TO BE ACCESSIBLE THEY SHALL
 MEET THE REQUIREMENTS11-4.16, 11-4.19, 11-4.20 AND
 11-4.23.
  
 6)INDICATE CLEARLY WEATHER THIS IS A TRANSIENT OR
 NONTRANSIENT FACILITY. SEE FBC 310.
  
 7)STATE WHAT TYPE OF MATERIALS WILL BE USED TO
 CONSTRUCT THE NEW STORAGE ROOM AND INDICATE THE TYPE
 AND QUANTITY OF MATERIALS WHICH WILL BE STORED. NOTE:
 THE WALLS MAY REQUIRE A FIRE RATING, DEPENDING ON THE
 STORED MATERIALS. ADDITIONAL INFORMATION IS REQUIRED.
 106.1.2*
  
 8)ALL SHEETS SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON TAKING RESPONSIBILITY FOR THE
 DRAWINGS. BUILDING PLANS SHALL BE DRAWN TO A MINIMUM
 1/8 INCH SCALE. 106.1.3
  