2008-06-11 08:39:13 | BUILDING PLAN REVIEW |
| PERMIT: 08060012 |
| ADD: 1117 N. ROSEMARY AVE. |
| CONT: KDN CONSTRUCTION SERVICES |
| TEL: (561)662-1002 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 1ST |
| ACTION: DENIED |
| |
| 1)WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 3)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE 2007 SUPPLEMENTS. |
| |
| 4) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN |
| OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| THIS CODE. |
| |
| 5)IF BOTH BATHROOMS ARE TO BE ACCESSIBLE THEY SHALL |
| MEET THE REQUIREMENTS11-4.16, 11-4.19, 11-4.20 AND |
| 11-4.23. |
| |
| 6)INDICATE CLEARLY WEATHER THIS IS A TRANSIENT OR |
| NONTRANSIENT FACILITY. SEE FBC 310. |
| |
| 7)STATE WHAT TYPE OF MATERIALS WILL BE USED TO |
| CONSTRUCT THE NEW STORAGE ROOM AND INDICATE THE TYPE |
| AND QUANTITY OF MATERIALS WHICH WILL BE STORED. NOTE: |
| THE WALLS MAY REQUIRE A FIRE RATING, DEPENDING ON THE |
| STORED MATERIALS. ADDITIONAL INFORMATION IS REQUIRED. |
| 106.1.2* |
| |
| 8)ALL SHEETS SHALL BEAR THE PRINTED NAME AND |
| SIGNATURE OF THE PERSON TAKING RESPONSIBILITY FOR THE |
| DRAWINGS. BUILDING PLANS SHALL BE DRAWN TO A MINIMUM |
| 1/8 INCH SCALE. 106.1.3 |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |