Plan Review Notes
Plan Review Notes For Permit 08050806
Permit Number 08050806
Review Stop E
Sequence Number 1
Notes
Date Text
2008-06-09 12:37:34 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 645.10 DISCONNECTING MEANS
 A MEANS SHALL BE PROVIDED TO DISCONNECT POWER TO ALL
 ELECTRONIC EQUIPMENT IN THE INFORMATION TECHNOLOGY
 EQUIPMENT ROOM. THERE SHALL ALSO BE A SIMILAR MEANS TO
 DISCONNECT THE POWER TO ALL DEDICATED HVAC SYSTEMS
 SERVING THE ROOM AND CAUSE ALL REQUIRED FIRE/SMOKE
 DAMPERS TO CLOSE. THE CONTROL FOR THESE DISCONNECTING
 MEANS SHALL BE GROUPED AND IDENTIFIED AND SHALL BE
 READILY ACCESSIBLE AT THE PRINCIPAL EXIT DOORS. A
 SINGLE MEANS TO CONTROL BOTH THE ELECTRONIC EQUIPMENT
 AND HVAC SYSTEMS SHALL BE PERMITTED. WHERE A PUSHBUTTON
 IS USED AS A MEANS TO DISCONNECT POWER, PUSHING THE
 BUTTON IN SHALL DISCONNECT THE POWER** SHOW THE
 LOCATION OF THESE DISCONNECTS FOR COMPLIANCE WITH THIS
 ARTICLE..
  
 2} 645.4(2)A SEPARATE
 HEATING/VENTILATING/AIR-CONDITIONING (HVAC) SYSTEM IS
 PROVIDED THAT IS DEDICATED FOR INFORMATION TECHNOLOGY
 EQUIPMENT USE AND IS SEPARATED FROM OTHER AREAS OF
 OCCUPANCY. ANY HVAC SYSTEM THAT SERVES OTHER
 OCCUPANCIES SHALL BE PERMITTED TO ALSO SERVE THE
 INFORMATION TECHNOLOGY EQUIPMENT ROOM IF FIRE/SMOKE
 DAMPERS ARE PROVIDED AT THE POINT OF PENETRATION OF THE
 ROOM BOUNDARY. SUCH DAMPERS SHALL OPERATE ON ACTIVATION
 OF SMOKE DETECTORS AND ALSO BY OPERATION OF THE
 DISCONNECTING MEANS REQUIRED BY 645.10.
  
 3} PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE
 SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718