2008-08-12 07:32:25 | BUILDING PLAN REVIEW |
| PERMIT: 08050784 |
| ADD: 1641 WORTHINGTON RD |
| CONT: HEDRICK BROTHERS |
| TEL: (561)662-0785 |
| |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| 08-12-08 |
| 2NDREVIEW |
| ACTION: DENIED |
| |
| 1)COMPLIED. |
| |
| 2) NOTE, BUILDING PROVISO:FBC BUILDING 3110.1.2 / |
| CITY OF WPB CODE OF ORDINANCES SECTION 94-546. |
| STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD |
| ELEVATION CERTIFICATE MAY BE REQUIRED. DEPENDING ON THE |
| TIMING OF THE BUILDING C.O. IF THE GENERATORS ARE GOING |
| TO BE CO'ED AT THE SAME TIME AS THE BUILDING A FLOOD |
| ZONE CERTIFICATE WILL BE REQUIRED. IF THE GENERATORS |
| ARE GOING TO BE FINALED AFTER THE BUILDING C.O. THEN |
| EITHER A SURVEY WITH ELEVATION HEIGTH OR DESIGNER OF |
| RECORD PROVIDING SITE PLAN WITH ASSCIATED SLAB |
| ELEVATION. THE MINIMUM FLOOD ELEVATION THE SLAB MAY BE |
| SET AT IS 13'-6" IN A "A-9" FLOOD ZONE, THIS MAY BE |
| ACCOMPLISHED AT TIME OF THE FINAL. |
| |
| 3) 2ND REQUEST, THERE ARE NO ARCHITECTURAL OR |
| STRUCTURAL PLANS INDICATING THE SIZE OFANCHOR FROM |
| THE EQUIPMENT PAD TO THE GENERATOR FRAME TO RESIST THE |
| MOMENT OF OVERTURNING. 1609. 1.3, ANCHORAGE AGAINST |
| MOMENT OF OVERTURNING, UPLIFT AND SLIDING. |
| |
| 4) COMPLIED. |
| |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |