2008-08-11 11:23:15PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLANS PAGE E5.1 GENERATOR SPECIFICATIONS LINE #4
 STATES THE FUEL TANK IS 500 GALLONS, THE BILL OF
 MATERIAL SUBMITTAL STATES THE FUEL TANK IS 1,215
 GALLONS. THE TWO MUST COINSIDE, PLEASE CORRECT.
  
 2) AS NOTED IN LAST REVIEW 6-23-08. SHOW ON PLAN SP-1,
 TYPE OF FUEL, FUEL TANK CAPACITY, AND LOCATION OF FUEL
 STORAGE TANK FOR GENERATOR, PER NFPA 30 4.3.2.1.
  
 3) AFTER CORRECTING PLANS THEY NEED TO BE SUBMITTED TO
 PALM BEACH COUNTY DEPT. OF ENVIRONMENTAL RESOURCES
 MANAGEMENT (D.E.R.M.) FOR REVIEW AND STAMPING, YOU MAY
 CALL (561) 233-2400 FOR MORE INFORMATION. THEN SUBMIT
 TO CITY OF W.P.B. BUILDING DEPT..
  