Plan Review Notes For Permit 08050784 |
Permit Number |
08050784 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-08-21 13:52:00 | ***DENIED*** | | | | 1) ADD NFPA 110, STANDARD FOR EMERGENCY POWER AND | | STANDBY SYSTEMS TO LIST OF CODES AND STANDARDS ON SHEET | | E0.1. RESPONSE LETTER INDICATES REVISED SHEET BUT CODE | | REFERENCE WAS NOT FOUND. | | | | 2) RESPONSE LETTER INDICATES THAT COMMENT WAS ADDRESSED | | BY KAMM CONSULTING. KAMM LETTER DOES NOT ADDRESS THIS | | ISSUE. | | | | 3) OK | | | | 4) FLOOR PLAN DOES NOT CLEARLY ILLUSTRATE THE LOCATION | | OF BUILDING OPENINGS WITH REGARD TO EXHAUST TERMINUS. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|