Plan Review Notes
Plan Review Notes For Permit 08050784
Permit Number 08050784
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-06-30 14:02:25***DENIED***
  
 1) ADD NFPA 110, STANDARD FOR EMERGENCY POWER AND
 STANDBY SYSTEMS TO LIST OF CODES AND STANDARDS ON SHEET
 E0.1.
  
 2) PLEASE IDENTIFY WHAT BUILDING SYSTEMS AND LIFE
 SAFETY EQUIPMENT WILL BE CONNECTED TO GENERATORS.
  
 3) SUBMIT MANUFACTURER SPECIFICATION SHEETS FOR
 GENERATORS AND ASSOCIATED EQUIPMENT.
  
 4) CLEARLY ILLUSTRATE LOCATION OF BUILDING OPENINGS AND
 EXIT DISCHARGE WITH RELATION TO EXHAUST TERMINATION.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW