Plan Review Notes For Permit 08050784 |
Permit Number |
08050784 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-06-30 14:02:25 | ***DENIED*** | | | | 1) ADD NFPA 110, STANDARD FOR EMERGENCY POWER AND | | STANDBY SYSTEMS TO LIST OF CODES AND STANDARDS ON SHEET | | E0.1. | | | | 2) PLEASE IDENTIFY WHAT BUILDING SYSTEMS AND LIFE | | SAFETY EQUIPMENT WILL BE CONNECTED TO GENERATORS. | | | | 3) SUBMIT MANUFACTURER SPECIFICATION SHEETS FOR | | GENERATORS AND ASSOCIATED EQUIPMENT. | | | | 4) CLEARLY ILLUSTRATE LOCATION OF BUILDING OPENINGS AND | | EXIT DISCHARGE WITH RELATION TO EXHAUST TERMINATION. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|