2008-08-08 10:42:05 | PLUMBING PLAN REVIEW: |
| DENIED **2ND TIME: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE |
| DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW |
| COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW |
| COMMENTS. |
| NOTE: THERE WAS NO COMMENT RESPONSE FROM THE |
| DESIGNER. |
| |
| 1. SHEET 2, PLUMBING HAS TWO DIFFERENT VENT SIZES |
| BEING INDICATED FOR THE POOL MAIN DRAIN, ONE AS BEING |
| 1" AND THE OTHER BEING 1-1/2", ALSO THE SPA MAIN DRAIN |
| VENT PIPING IS BEING INDICATED AS 1-1/2", HOWEVER THE |
| "ENTRAPMENT AVOIDANCE VENT PIPE ANALYSIS - MAXIMUM |
| LENGTH" SHEET IS ONLY INDICATING A VENT PIPE TABLE FOR |
| 1" PIPE. PLEASE CORRELATE AND CORRECT RESUBMITTED |
| SHEETS WITH VENT PIPE SIZES. PER (W.P.B. AS AMENDED) |
| SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| **PREVIOUS COMMENT HAS NOT BEEN ADDRESSED. THE |
| RESUBMITTED PLANS ARE INDICATING AN 1-1/2" VENT, |
| HOWEVER THE ENTRAPMENT AVOIDANCE VENT PIPE |
| ANALISIS-MAXIMUM LENGTH DETAIL IS FOR A 1" VENT PIPE. |
| AS REQUESTED IN THE FIRST PLAN REVIEW PLEASE CORRELATE |
| ALL SHEETS TO REFLECT THE SAME VENT PIPE SIZE. PER |
| (W.P.B. AS AMENDED) SECTION 106.1.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS AND FBC-2004 RESIDENTIAL CHAPTER |
| 41, SECTION R4101.6 ENGINEERING DESIGN. |
| |
| 2. "OK" COMMENT ADDRESSED |
| |
| 3. "OK" COMMENT ADDRESSED. |
| |
| **THE FOLLOWING IS A NEW COMMENT** |
| |
| 4. SEE ATTACHED NOTICE FS 553.80(2)(B) REGARDING FOUR |
| TIMES THE FEE. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |