Date |
Text |
2008-06-05 16:07:56 | PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. SHEET P-1.0 WATER RISER DIAGRAM: CLEARLY IDENTIFY |
| WHAT IS BEING INSTALLED AT EACH FIXTURE FOR WATER |
| HAMMER. SHEET P-2.0 GENERAL PLUMBING NOTES #17 STATES |
| "CONTRACTOR SHALL PROVIDE MAINTENANCE FREE MECHANICAL |
| SHOCK ARRESTORS AT ALL FIXTURES WITH QUICK CLOSING |
| VALVES", HOWEVER NOT ALL THE FIXTURES INDICATED IN THE |
| WATER RISER DIAGRAM ARE QUICK CLOSING (POSSIBLY ONLY |
| THE REF. IF IT HAS AN ICE MAKER) . AIR CHAMBERS ARE NOT |
| ACCEPABLE UNLESS THEY ARE PER "STANDARD PDI-WH 201, A |
| RECHARGABLE TYPE OF AIR CHAMBER"(DETAIL REQUIRED). |
| PER FBC- 2004 PLUMBING SECTION 604.9 WATER HAMMER. |
| |
| 2. SHEET A-2.01 DETAIL #3: CLEARLY INDICATE THE KNEE |
| CLEARANCE COMPLIANT WITH FBC-2004 CHAPTER 11 SECTION |
| 11-4.24.3 (27" HIGH, 30" WIDE, AND 19" DEEP SHALL BE |
| PROVIDED UNDERNEATH SINKS. |
| |
| 3. SHEET A-1.01 THIRD FLOOR PLAN: CLEARLY INDICATE THE |
| CLEAR FLOOR SPACE FOR THE SINK IN KITCHENETTE ROOM #114 |
| COMPLIANT WITH FBC-2004 CHAPTER 11 SECTION 11-4.24.5 |
| (30" X 48" AND SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH |
| THE SINK). |
| |
| 4. SHEET A-2.01 DETAIL #2 ADA FOUNTAIN: |
| 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS |
| PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN |
| WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS |
| IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE |
| TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS |
| CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR |
| BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED |
| ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR SUCH AS A |
| CUP HOLDER). |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| PHONE= (561) 805-6730 |
| FAX= (561) 805-6731 |
| E-MAIL= [email protected] |
| |