Plan Review Notes
Plan Review Notes For Permit 08050719
Permit Number 08050719
Review Stop P
Sequence Number 1
Notes
Date Text
2008-06-05 11:58:39PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET P-1.0 PLUMBING FLOOR PLAN, SANITARY AND WATER
 RISER DIAGRAMS: CLEARLY IDENTIFY ALL FIXTURES AS TWO
 ARE NOT IDENTIFIED ON THE PLUMBING FLOOR PLAN AND ONE
 IS NOT IDENTIFIED ON THE SANITARY AND WATER RISER
 DIAGRAMS IN KITCHEN #109. PER FBC-2004 PLUMBING SECTION
 601.1 SCOPE AND SECTION 701.1 SCOPE.
  
 2. SHEET P-1.0 WATER RISER DIAGRAM: CLEARLY IDENTIFY
 WHAT IS BEING INSTALLED AT EACH FIXTURE FOR WATER
 HAMMER. SHEET P-2.0 GENERAL PLUMBING NOTES #17 STATES
 "CONTRACTOR SHALL PROVIDE MAINTENANCE FREE MECHANICAL
 SHOCK ARRESTORS AT ALL FIXTURES WITH QUICK CLOSING
 VALVES", HOWEVER THE FIXTURES INDICATED IN THE WATER
 RISER DIAGRAM ARE NOT QUICK CLOSING. AIR CHAMBERS ARE
 NOT ACCEPABLE UNLESS THEY ARE PER "STANDARD PDI-WH 201,
 A RECHARGABLE TYPE OF AIR CHAMBER"(DETAIL REQUIRED).
 PER FBC- 2004 PLUMBING SECTION 604.9 WATER HAMMER.
  
 3. SHEET A-2.01 DETAIL #3: CLEARLY INDICATE THE KNEE
 CLEARANCE COMPLIANT WITH FBC-2004 CHAPTER 11 SECTION
 11-4.24.3 (27" HIGH, 30" WIDE, AND 19" DEEP SHALL BE
 PROVIDED UNDERNEATH SINKS.
  
 4. SHEET 1A-1.01 THIRD FLOOR PLAN: CLEARLY INDICATE
 THE CLEAR FLOOR SPACE FOR THE SINK IN KITCHEN #109 AND
 AND SINK ACROSS FROM ROOM #105 COMPLIANT WITH FBC-2004
 CHAPTER 11 SECTION 11-4.24.5 (30" X 48" AND SHALL
 EXTEND A MAXIMUM OF 19" UNDERNEATH THE SINK).
  
 5. SHEET P-2.0 PLUMBING FIXTURE CONNECTION SCHEDULE:
 FIXTURE P-4 DISCRIPTION IS BEING INDICATED AS A SERVICE
 SINK WITH A 2" WASTE. ISN'T THIS A 6-1/2" DEEP
 STAINLESS STEEL SINK WITH A 1-1/2" WASTE. PLEASE
 CLARIFY THIS ON THE RESUBMITTAL. PER FBC-2004 PLUMBING
 SECTION 401.1 SCOPE.
  
 6. SHEET A-2.01 DETAIL #2 ADA FOUNTAIN: PER
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR SUCH AS A
 CUP HOLDER).
  
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  