| BUILDING PLAN REVIEW |
| PERMIT: 08050719 |
| ADD: 2475 MERCER AVE #301- 302 B |
| CONT: PHILLIP E JOHNSON INC. |
| TEL: (561)366-1034 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 6-2-08 |
| REVIEW: 1ST |
| ACTION: DENIED |
| |
| 1)WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2)106.3.5.1.1(5), FS 553.79(2) FIRE SPRINKLER PLANS |
| REQUIRED. |
| PROVIDE A FIRE SPRINKLER LAYOUT SHOWING THE SPRINKLER |
| HEADS IN REFERENCE TO THE NEW WALLS BEING CONSTRUCTED. |
| THIS MAY BE SHOWN ON THE REFLECTED CEILING PLANS |
| |
| 3)SHOW THE ELEVATION OF THE RECEPTIONIST WINDOW |
| SHOWING ALL DIMENSIONS MEETING THE REQUIREMENTS OF FBC |
| SECTION 11-7 WHERE A PORTION OF THE COUNTER SHALL HAVE |
| A MAXIMUM HEIGHT OF 36 INCHES AND MINIMUM WIDTH OF 36 |
| INCHES WHEN SERVICES ARE RENDERED TO THE PUBLIC. |
| |
| 4)ADDITIONAL INFORMATION IS REQUIRED FOR THE ROOM |
| FINISHES; INDICATING WHICH WALL RECEIVES THE REQUIRED |
| FINISH. THE SCHEDULE PROVIDED IS NOT CLEAR, AND THERE |
| ARE NOT ROOM NUMBERS ON THE SCHEDULE. NOTE: 1210.2 |
| WALLS WITHIN 2 FEET OF URINALS AND WATER CLOSETS SHALL |
| HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT |
| OF 4 FEET ABOVE THE FINISH FLOOR. |
| |
| 5) INDICATE THE VERTICAL ACCESSIBILITY FOR THE BUILDING |
| ON THE DRAWINGS. FBC 11-4.1.3(5) ONE PASSENGER ELEVATOR |
| COMPLYING WITH 11-4.10 SHALL SERVE EACH LEVEL, |
| INCLUDING MEZZANINES, IN ALL MULTISTORY BUILDINGS AND |
| FACILITIES. |
| |