Plan Review Notes For Permit 08050698 |
Permit Number |
08050698 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-06-10 13:45:47 | ***DENIED*** | | | | 1) PLANS SHALL MEET THE REQUIREMENTS OF SEC. 106.1.3 IN | | THE AMENDMENTS TO THE 2004 FBC, AND SHALL BE DRAWN TO A | | MINIMUM OF 1/8 INCH SCALE. SOME AREAS DIFFICULT TO | | READ. | | | | 2) DOCUMENTS TO INCLUDE SPEC/CUT SHEETS, PRODUCT | | APPROVALS, CALCULATIONS ETC. SHALL NOT BE ATTACHED TO | | PLANS. | | | | 3) FIRE ALARM SYSTEM TO BE UL CERTIFIED FOR CENTRAL | | STATION SERVICE. UL CERTIFICATE WILL BE REQUIRED PRIOR | | TO FINAL INSPECTION. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|