Plan Review Notes
Plan Review Notes For Permit 08050667
Permit Number 08050667
Review Stop Z
Sequence Number 1
Notes
Date Text
2008-05-30 10:02:59***FAILED***
  
  
 1)AS THE SURVEY DOES NOT SHOW AN EXISTING PERMANENT
 FENCE COMPLETELY SURROUNDING THE POOL (EAST SIDE NOT
 ENCLOSED), A FENCE PERMIT SHALL BE SUBMITTED
 CONCURRENTLY AND SHALL CONFORM TO THE MINIMUM STANDARDS
 PROVIDED BELOW.
  
 PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS), SECTION,
 94-304(D)(2)(B)+(C):
  
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
  
 2)INDICATE SETBACK DIMENSIONS FROM PROPOSED POOL
 EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720