2008-05-27 13:48:38 | GAS PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. THE VALUE ON THE PERMIT APPLICATION APPEARS LOW. |
| THE VALUE ON THE PERMIT APPLICATION MUST INCLUDE THE |
| TOTAL COST OF LABOR AND MATERIALS. VALUATION REFERENCES |
| MAY INCLUDE THE LATEST PUBLISHED DATA OF A NATIONAL |
| CONSTRUCTION COST ANALYSIS (MARSHALL-SWIFT, MEANS, |
| ECT...) ADJUST THE VALUE AT THE PERMIT CLERK'S DESK AND |
| PAY THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING OR |
| PROVIDE A COPY OF THE SIGNED CONRACT BY BOTH PARTIES |
| (CONTRACTOR AND CUSTOMER) TO VERIFY THE PERMIT |
| APPLICATION VALUE. PER (W.P.B. AS AMENDED) SECTION |
| 108.3 BUILDING PERMIT VALUATION. |
| |
| 2. THE SUBMITTED FLOOR PLAN FOR THE GAS PIPING HAS AN |
| ARCHITECT'S TITLE BLOCK. |
| PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| FL ADMIN CODE 61G16.003 ARCHITECTS |
| |
| 3. THE SUBMITTED GAS ISOMETRIC DOES NOT HAVE |
| CORRESPONDING LENGTHS BEING INDICATED FOR ALL CUT |
| SECTIONS OF PIPE. PLEASE REFERENCE THE RED CIRCLED |
| YELLOW HIGH LIGHTED CUT SECTIONS WITHOUT CORRESPONDING |
| LENGTHS BEING INDICATED. A GAS PLAN REVIEW CAN NOT BE |
| DONE UNLESS ALL CUT SECTION OF PIPE HAVE CORRESPONDING |
| LENGTHS INDCATED. PER FBC-2004 FUEL GAS SECTION 401.1. |
| |
| 4. THE SUBMITTED GAS ISOMETRIC DOES NOT HAVE ALL CUT |
| SECTIONS OF PIPE BEING SIZED. PLEASE REFERENCE THE CSST |
| PIPING FROM THE 1-1/4"X1"X1" BLK/STEEL TEE TO THE |
| 77,000 BTU WATER HEATER THAT NOT SIZED. PLEASE SIZE ALL |
| CUT SECTIONS OF PIPE ON THE RESUBMITTAL. PER FBC-2004 |
| FUEL GAS SECTION 401.1 SCOPE. |
| |
| 5. CLEARLY INDICATE THAT ALL FUTURE APPLIANCES WILL BE |
| CAPPED GAS TIGHT (FUTURE POOL HEATER AND FUTURE FIRE |
| PLACE). PER FBC-2004 FUEL GAS SECTION 404.12 OUTLET |
| CLOSURES. |
| |
| 6. PLEASE INDICATE ON THE RESUBMITTED FLOOR PLAN THAT |
| THE GAS WATER HEATER IN THE 1 CAR GARAGE WILL BE |
| PROTECTED FROM PHYSICAL DAMAGE BY APPROVED BARRIERS. |
| PER FBC-2004 FUEL GAS SECTION 303.4 PROTECTIN FRO |
| PHYSICAL DAMAGE. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| PHONE= (561) 805-6730 |
| FAX= (561) 805-6731 |
| E-MAIL= [email protected] |