Plan Review Notes
Plan Review Notes For Permit 08050662
Permit Number 08050662
Review Stop G
Sequence Number 1
Notes
Date Text
2008-05-27 13:48:38GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE VALUE ON THE PERMIT APPLICATION APPEARS LOW.
 THE VALUE ON THE PERMIT APPLICATION MUST INCLUDE THE
 TOTAL COST OF LABOR AND MATERIALS. VALUATION REFERENCES
 MAY INCLUDE THE LATEST PUBLISHED DATA OF A NATIONAL
 CONSTRUCTION COST ANALYSIS (MARSHALL-SWIFT, MEANS,
 ECT...) ADJUST THE VALUE AT THE PERMIT CLERK'S DESK AND
 PAY THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING OR
 PROVIDE A COPY OF THE SIGNED CONRACT BY BOTH PARTIES
 (CONTRACTOR AND CUSTOMER) TO VERIFY THE PERMIT
 APPLICATION VALUE. PER (W.P.B. AS AMENDED) SECTION
 108.3 BUILDING PERMIT VALUATION.
  
 2. THE SUBMITTED FLOOR PLAN FOR THE GAS PIPING HAS AN
 ARCHITECT'S TITLE BLOCK.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 3. THE SUBMITTED GAS ISOMETRIC DOES NOT HAVE
 CORRESPONDING LENGTHS BEING INDICATED FOR ALL CUT
 SECTIONS OF PIPE. PLEASE REFERENCE THE RED CIRCLED
 YELLOW HIGH LIGHTED CUT SECTIONS WITHOUT CORRESPONDING
 LENGTHS BEING INDICATED. A GAS PLAN REVIEW CAN NOT BE
 DONE UNLESS ALL CUT SECTION OF PIPE HAVE CORRESPONDING
 LENGTHS INDCATED. PER FBC-2004 FUEL GAS SECTION 401.1.
  
 4. THE SUBMITTED GAS ISOMETRIC DOES NOT HAVE ALL CUT
 SECTIONS OF PIPE BEING SIZED. PLEASE REFERENCE THE CSST
 PIPING FROM THE 1-1/4"X1"X1" BLK/STEEL TEE TO THE
 77,000 BTU WATER HEATER THAT NOT SIZED. PLEASE SIZE ALL
 CUT SECTIONS OF PIPE ON THE RESUBMITTAL. PER FBC-2004
 FUEL GAS SECTION 401.1 SCOPE.
  
 5. CLEARLY INDICATE THAT ALL FUTURE APPLIANCES WILL BE
 CAPPED GAS TIGHT (FUTURE POOL HEATER AND FUTURE FIRE
 PLACE). PER FBC-2004 FUEL GAS SECTION 404.12 OUTLET
 CLOSURES.
  
 6. PLEASE INDICATE ON THE RESUBMITTED FLOOR PLAN THAT
 THE GAS WATER HEATER IN THE 1 CAR GARAGE WILL BE
 PROTECTED FROM PHYSICAL DAMAGE BY APPROVED BARRIERS.
 PER FBC-2004 FUEL GAS SECTION 303.4 PROTECTIN FRO
 PHYSICAL DAMAGE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  