Plan Review Notes For Permit 08050661 |
Permit Number |
08050661 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-07-30 15:08:55 | ***DENIED*** | | | | 1) OK | | | | 2) PLEASE PROVIDE LAYOUT OF FIRE SPRINKLER COVERAGE. | | SEE BUILDING COMMENT #5. | | | | 3) NOT ADDRESSED. DUCT SMOKE DETECTORS SHALL INITIATE A | | GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL | | REQUIREMENTS. AMEND FIRE ALARM NOTE #17 ON SHEET | | FA0.1. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|