Plan Review Notes
Plan Review Notes For Permit 08050661
Permit Number 08050661
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2008-07-30 15:08:55***DENIED***
  
 1) OK
  
 2) PLEASE PROVIDE LAYOUT OF FIRE SPRINKLER COVERAGE.
 SEE BUILDING COMMENT #5.
  
 3) NOT ADDRESSED. DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL
 REQUIREMENTS. AMEND FIRE ALARM NOTE #17 ON SHEET
 FA0.1.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW