Plan Review Notes For Permit 08050661 |
Permit Number |
08050661 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-06-19 13:30:30 | REVIEW #: 1ST | | ACTION: DENIED | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. M0.1: NOTE #15, SMOKE DETECTORS SHALL BE TIED TO THE | | BUILDING FIRE ALARM SYSTEMS IN ACCORDANCE WITH FBCM | | 606.4.1. | | | | 2. M2.1: NEW BATHROOM EXHAUST FAN HAS AN EXHAUST DUCT | | IN THE PLENUM WHICH IS UNDER POSITIVE PRESSURE. EXHAUST | | DUCTS UNDER POSITIVE PRESSURE SHALL NOT EXTEND INTO OR | | PASS THROUGH DUCTS OR PLENUMS IN ACCORDANCE WITH FBCM | | 601.3. | | | | 3. M2.1: THE OUTDOOR AIR SUPPLY SYSTEM SHALL BE | | EQUIPPED WITH A MOTORIZED DAMPER THAT WILL | | AUTOMATICALLY SHUT WHEN THE SYSTEM OR SPACE SERVED IS | | NOT IN USE IN ACCORDANCE WITH FBCB 13-409.1.ABC.3.3. | | | | 4. M5.1: OUTSIDE AIR CLACULATIONS SHOW A DESIGN BASED | | ON ASHRAE 62-01. OUTSIDE AIR CALCULATIONS SHALL BE | | DETERMINED IN ACCORDANCE WITH FBCM TABLE 403.3 OR | | ASHRAE 62.1-2004 IN ACCORDANCE WITH FBCM 403.4. | | | | 5. M5.1: HEAT PUMP SCHEDULE, ACH HYDRONIC HEAT PUMP | | SHALL HAVE A TWO-POSITION AUTOMATIC VALVE INTERLOCKED | | TO SHUT OFF WATER FLOW WHEN THE COMPRESSOR IS OFF IN | | ACCORDANCE WITH FBCB 13-411.1.ABC.1.4. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|