Plan Review Notes
Plan Review Notes For Permit 08050661
Permit Number 08050661
Review Stop M
Sequence Number 1
Notes
Date Text
2008-06-19 13:30:30REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. M0.1: NOTE #15, SMOKE DETECTORS SHALL BE TIED TO THE
 BUILDING FIRE ALARM SYSTEMS IN ACCORDANCE WITH FBCM
 606.4.1.
  
 2. M2.1: NEW BATHROOM EXHAUST FAN HAS AN EXHAUST DUCT
 IN THE PLENUM WHICH IS UNDER POSITIVE PRESSURE. EXHAUST
 DUCTS UNDER POSITIVE PRESSURE SHALL NOT EXTEND INTO OR
 PASS THROUGH DUCTS OR PLENUMS IN ACCORDANCE WITH FBCM
 601.3.
  
 3. M2.1: THE OUTDOOR AIR SUPPLY SYSTEM SHALL BE
 EQUIPPED WITH A MOTORIZED DAMPER THAT WILL
 AUTOMATICALLY SHUT WHEN THE SYSTEM OR SPACE SERVED IS
 NOT IN USE IN ACCORDANCE WITH FBCB 13-409.1.ABC.3.3.
  
 4. M5.1: OUTSIDE AIR CLACULATIONS SHOW A DESIGN BASED
 ON ASHRAE 62-01. OUTSIDE AIR CALCULATIONS SHALL BE
 DETERMINED IN ACCORDANCE WITH FBCM TABLE 403.3 OR
 ASHRAE 62.1-2004 IN ACCORDANCE WITH FBCM 403.4.
  
 5. M5.1: HEAT PUMP SCHEDULE, ACH HYDRONIC HEAT PUMP
 SHALL HAVE A TWO-POSITION AUTOMATIC VALVE INTERLOCKED
 TO SHUT OFF WATER FLOW WHEN THE COMPRESSOR IS OFF IN
 ACCORDANCE WITH FBCB 13-411.1.ABC.1.4.
  