Plan Review Notes
Plan Review Notes For Permit 08050661
Permit Number 08050661
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-06-25 14:31:38*****PROVISO*****
  
 THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN THE
 BELOW COMMENTS HAVE BEEN ADDRESSED:
  
 1.SHOW THE LOCATION OF THE 2A10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATIFIES THE 75' TRAVEL
 DISTANCE.
  
 2.PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS FOR
 THE NEW FLOOR PLAN.
  
 3.AMEND FIRE ALARM NOTE #17 (ON SHEET FA0.1) TO
 REFLECT THAT DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW