Plan Review Notes For Permit 08050661 |
Permit Number |
08050661 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-06-25 14:31:38 | *****PROVISO***** | | | | THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN THE | | BELOW COMMENTS HAVE BEEN ADDRESSED: | | | | 1.SHOW THE LOCATION OF THE 2A10BC RATED FIRE | | EXTINGUISHER(S) WHICH SATIFIES THE 75' TRAVEL | | DISTANCE. | | | | 2.PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS FOR | | THE NEW FLOOR PLAN. | | | | 3.AMEND FIRE ALARM NOTE #17 (ON SHEET FA0.1) TO | | REFLECT THAT DUCT SMOKE DETECTORS SHALL INITIATE A | | GENERAL FIRE ALARM. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | |
|