Date |
Text |
2008-06-20 12:49:09 | ** DENIEDREVIEW ** |
| |
| |
| 1) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1, .1.2. |
| |
| 2) NOTE: PLEASE INDICATE MAXIMUM OVER RIDE TIMES FOR |
| DEVICES AS SHOWN. PLEASE COORDINATE SYMBOL LEGEND. |
| PLEASE SEE THE SYMBOL LEGEND MENTIONS TO SEE DETAIL ON |
| E7.1 HOWEVER NO ELECTRICAL SHEET E7.1 WAS IN SET OR |
| SUBMITTED. |
| |
| 3) NOTE: PLEASE SEE PANEL LA AS SHOWN IS A *MAIN LUG |
| ONLY* PANEL. THIS SHALL CONTAIN OVER CURRENT PROTECTION |
| ON THE SECONDARY SIDE OF THE TRANSFORMER. |
| 240.21, 408.36, 240.4, 310.16 ETC |
| ** NOTE ON TRANSFORMER SCHEDULE STATES THE BREAKER ON |
| SECONDARY PANEL HAS MAIN BUT DOES NOT COORDINATE WITH |
| OTHER ITEMS ON SAME SHEET. |
| |
| IF A MAIN BREAKER DOES NOT EXIST ONE WILL BE REQUIRED |
| AS THIS IS A FIRE AND LIFE SAFETY HAZARD. |
| |
| |
| |
| ** IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| HESITATE IN CONTACTING THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |