Plan Review Notes
Plan Review Notes For Permit 08050661
Permit Number 08050661
Review Stop E
Sequence Number 1
Notes
Date Text
2008-06-20 12:49:09** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1, .1.2.
  
 2) NOTE: PLEASE INDICATE MAXIMUM OVER RIDE TIMES FOR
 DEVICES AS SHOWN. PLEASE COORDINATE SYMBOL LEGEND.
 PLEASE SEE THE SYMBOL LEGEND MENTIONS TO SEE DETAIL ON
 E7.1 HOWEVER NO ELECTRICAL SHEET E7.1 WAS IN SET OR
 SUBMITTED.
  
 3) NOTE: PLEASE SEE PANEL LA AS SHOWN IS A *MAIN LUG
 ONLY* PANEL. THIS SHALL CONTAIN OVER CURRENT PROTECTION
 ON THE SECONDARY SIDE OF THE TRANSFORMER.
 240.21, 408.36, 240.4, 310.16 ETC
 ** NOTE ON TRANSFORMER SCHEDULE STATES THE BREAKER ON
 SECONDARY PANEL HAS MAIN BUT DOES NOT COORDINATE WITH
 OTHER ITEMS ON SAME SHEET.
  
 IF A MAIN BREAKER DOES NOT EXIST ONE WILL BE REQUIRED
 AS THIS IS A FIRE AND LIFE SAFETY HAZARD.
  
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]