2008-06-25 10:58:26BUILDING PLAN REVIEW
 PERMIT: 08050661
 ADD: 515 N. FLAGLER DR. P-100
 CONT: FISHER CONTRACTING CORP.
 TEL: (561)691-4718
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS.
  
 3)THE CONSTRUCTION TYPE OF BUILDING INDICATED ON THE
 DRAWINGS IS TYPE II. THIS BUILDING IS OVER 20 STORIES
 HIGH, THEREFORE, THE BUILDING WILL BE A TYPE I
 CONSTRUCTION TYPE PER FBC SECTION 503 TABLE 503.
 CHAPTER 6 SHALL ALSO BE LOOK AT FOR MORE INFORMATION.
  
 4) 106.1.2*ADDITIONAL INFORMATION IS REQUIRED FOR FOR
 THE NEW SOFFIT. PROVIDE THE FRAMING DETAILS SHOWING HOW
 IT WILL BE FASTENED TO THE EXISTING STRUCTURE.
  
 5)NOTE: ONE SET OF THE DRAWINGS IS MISSING SHEET
 A-6.1. PROVIDE A FIRE SPRINKLER PLAN SHOWING THE
 LOCATION OF THE SPRINKLER HEADS IN RELATION TO THE NEW
 CONSTRUCTION. THIS INFORMATION CAN BE SHOWN ON THE
 REFLECTED CEILING PLANS. FBC106.3.5.1.1(5)
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER