Plan Review Notes
Plan Review Notes For Permit 08050629
Permit Number 08050629
Review Stop E
Sequence Number 2
Notes
Date Text
2008-07-25 14:37:39*** NOTE ADDED ***
  
 1) NOTE: PLEASE COORIDNATE SUITE/UNIT ON PLANS AS
 PERMIT APPLICATION AND ARCHITECTURAL SHEETS SHOW SUITE
 #1500 YET MEP PLANS INDICATE SUITE #1501. THIS CAN BE
 NEATLY HAND PRINTED ON SHEETS WHICH DO NOT NEED TO BE
 RE-PRINTED FOR COMMENTS.
 FAC 61G1-16.004, 61G15-23.002, FBC 106.5
2008-07-25 14:16:31** DENIED **
  
 ** PLEASE SEE THE FOLLOWING ITEMS ARE NEW COMMENTS
 BASED ON PLANS (ELECTRICAL RISER/SERVICE) BEING
 COMPLETELY REVISED FROM PREVIOUS SUBMITTED PLANS. AS
 THE PREVIOUS PLANS DID NOT CONTAIN THESE NEW ELECTRICAL
 PANELS, GUTTERS, MAINS ETC THESE ITEMS WERE NOT
 REVIEWED ON INITIAL REVIEW. ALL SERVICE EQUIPMENT ON
 PREVIOUS PLANS WERE SHOWN AS EXISTING.
  
 1) NOTE: PLEASE SEE PANEL *H* WHICH ON SCHEDULE IS
 SHOWING TO BE A 200AMP MAIN CIRCUIT BREAKER PANEL YET
 THE RISER MENTIONS THIS PANEL WILL NOW BE BACK FED TO
 THE EXISTING 150AMP SUB BRANCH BREAKER.THE RISER
 SHOWS 1/0 CONDUCTORS WHICH ARE NOW BEING FED FROM THE
 NEW GUTTER. IF PANEL *H* CONTAINS THE 200AMP MAIN
 CIRCUIT BREAKER AS STATED ON SCHEDULE THE CONDUCTORS
 ARE NOT OF SUFFICIENT SIZE PER 240.21,310.16,110.14.
 PLEASE ADJUST.
  
 2) NOTE: PLEASE SEE PANEL *H* AS THIS PANEL SHOWS 3/0
 CONDUCTORS YET THE RISER SHOWS 1/0 TAPPED CONDUCTORS.
 DEPENDING ON OVER CURRENT PROTECTION FOR TAPPED
 CONDUCTORS ARE NOTED ABOVE IN NOTE #1 THIS WILLNEED
 TO CHANGE AND COORDINATE.
 240.21,310.16 ETC
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 3) NOTE: PLEASE SEE THE NEW PANEL *S* WHICH BASED ON
 THE PANEL SCHEDULE IT SHOWS NEW FEEDERS TO BE 4-#3 AND
 1#8 FOR EQUIPMENT GROUNDING HOWEVER BASED ON THE RISER
 THE FEEDERS ARE SHOWN AS 4-#6 AND 1-#10 EQUIPMENT
 GROUND. PANEL SCHEDULE R1 STATES #6.
 PLEASE ALSO SEE THE PANEL IS NOTING THIS AS AN 18
 CIRCUIT PANEL YET THE PANEL IS SHOWN AS 42 CIRCUIT.
 WHICH WILL BE THE FEEDERS?
 310.16,240.4 ETC
 FBC 106.1.1, 106.1.2 FOR CLARITY AND COORDINATION.
  
 4) NOTE: PLEASE SEE PANEL *R1* AS THE RISER SHOWS THIS
 PANEL AS A 400AMP RATED PANEL WITH 400AMP MAIN CIRCUIT
 BREAKER YET THE PANEL *R1* SHOWS THIS PANEL AS A 225AMP
 RATED PANEL WITH A 200AMP MAIN. BASED ON THE LOAD ON
 PANEL THE PANEL MAY NOT CONTAIN A 200AMP BREAKER. THE
 LOAD EXCEEDS THE RATING OF THE 200AMP MAIN. PLEASE ALSO
 SEE THIS SAME PANEL IS NOTED WITH 30 CIRCUITS YET
 SCHEDULE INDICATES 42 CIRCUITS. CAN NOT BE 30 CIRCUITS
 AS THERE ARE BRANCH CIRCUITS SHOWN ABOVE THE 30
 CIRCUITS ON SCHEDULE.
 PLEASE ADJUST ALL DEVICES, PANEL RATINGS, MAINS,
 CIRCUITS ETC.
 240.21,408.36, 408.4 ETC
 FBC 106.1.1, 106.1.2 FOR CLARITY AND COORDINATION.
  
 5) NOTE: PLEASE SEE PANEL *H* WHICH STILL INDICATES A
 150AMP SUB BRANCH BREAKER TO FEED EXISTING TRANSFORMER
 YET THE RISER SHOWS THE TRANSFORMER NOW BEING FED FROM
 A NEW MAIN DISCONNECT TAPPED FROM THE GUTTER. BASED ON
 REVISED RISER THE TRANSFORMER IS NO LONGER BEING FED
 FROM PANEL *H*.
 408.4
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 6) NOTE: PLEASE SEE PREVIOUS COMMENTS IN REFERENCE TO
 ROOM 1514 WHICH IS NOTED ON PLANS AS A SERVER ROOM.
 THIS ROOM HAS SEPARATE AC EQUIPMENT, SEPARATE PANEL
 FEEDING TWO SERVERS AND THE RESPONSE WAS THE EPO BUTTON
 WAS REMOVED. THE PREVIOUS REVIEW NOTED STATED THAT IF
 THIS IS NOT AN IT ROOM BY NEC 645 DEFINITIONS THEN
 PLACE NOTE ON PLANS THAT WIRING METHODS IN NEC 645 ARE
 NOT PERMITTED. WIRING METHODS UNDER NEC 645 ARE LESS
 STRINGENT THAN CHAPTERS 1-4.
  
 7) NOTE: PLEASE SEE PANELS R2 AND R3 ARE BOTH SHOWN AS
 200AMP MAIN CIRCUIT BREAKER PANELS YET THE RISER SHOWS
 BOTH AS MAIN LUG ONLY.
 PLEASE COORDINATE.
 408
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 8) NOTE: PLEASE SEE THE MAIN ELECTRICAL ROOM HAS NOT
 BEEN REVISED ON PLANS TO SHOW NEW EQUIPMENT WITH NEW
 LOCATIONS.
 240.24, 110.26
 FBC 106.3.5.1.2, 106.1.1
  
 9) NOTE: PLEASE SEE THE FIXTURE *H* WHICH WAS MISSING
 THE FIXTURE DESIGNATION ON PREVIOUS PLANS INDICATES THE
 LIGHTING CONTROL CIRCUIT TO G2-2, YET THE SCHEDULE
 SHOWN ON E-5 DOES NOT LIST THE FIXTURE *H* UNDER G2-2
 ONLY FIXTURES *B* AND *BE* ARE LISTED.
 PLEASE REVISE CIRCUITING ON SCHEDULES ON SHEET E-5 AS
 THIS IS A NEW SHEET WITH NEW CIRCUITS FOR LIGHTING
 WHICH WAS NOT PART OF THE PREVIOUS REVIEWED PLANS. THIS
 IS NOT THE ONLY CIRCUIT WHICH DOES NOT COORDINATE. AN
 ADDITIONAL EXAMPLE IS CIRCUIT G2-6 AS THIS IS SHOWN AS
 A SPARE ON SHEET E-5 YET PLEASE SEE CORRIDOR 1510 ON
 PLANS AS FIXTURES *C* ARE CLEARLY SHOWN WITH THIS SAME
 CIRCUIT.
 PLEASE BE SURE TO GO OVER ALL NEW CIRCUITING AND
 SCHEDULE..
 FBC 13-415.1.ABC.1.1, .1.3.
 FBC 106.1.1.1
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  