Date |
Text |
2008-07-25 14:37:39 | *** NOTE ADDED *** |
| |
| 1) NOTE: PLEASE COORIDNATE SUITE/UNIT ON PLANS AS |
| PERMIT APPLICATION AND ARCHITECTURAL SHEETS SHOW SUITE |
| #1500 YET MEP PLANS INDICATE SUITE #1501. THIS CAN BE |
| NEATLY HAND PRINTED ON SHEETS WHICH DO NOT NEED TO BE |
| RE-PRINTED FOR COMMENTS. |
| FAC 61G1-16.004, 61G15-23.002, FBC 106.5 |
2008-07-25 14:16:31 | ** DENIED ** |
| |
| ** PLEASE SEE THE FOLLOWING ITEMS ARE NEW COMMENTS |
| BASED ON PLANS (ELECTRICAL RISER/SERVICE) BEING |
| COMPLETELY REVISED FROM PREVIOUS SUBMITTED PLANS. AS |
| THE PREVIOUS PLANS DID NOT CONTAIN THESE NEW ELECTRICAL |
| PANELS, GUTTERS, MAINS ETC THESE ITEMS WERE NOT |
| REVIEWED ON INITIAL REVIEW. ALL SERVICE EQUIPMENT ON |
| PREVIOUS PLANS WERE SHOWN AS EXISTING. |
| |
| 1) NOTE: PLEASE SEE PANEL *H* WHICH ON SCHEDULE IS |
| SHOWING TO BE A 200AMP MAIN CIRCUIT BREAKER PANEL YET |
| THE RISER MENTIONS THIS PANEL WILL NOW BE BACK FED TO |
| THE EXISTING 150AMP SUB BRANCH BREAKER.THE RISER |
| SHOWS 1/0 CONDUCTORS WHICH ARE NOW BEING FED FROM THE |
| NEW GUTTER. IF PANEL *H* CONTAINS THE 200AMP MAIN |
| CIRCUIT BREAKER AS STATED ON SCHEDULE THE CONDUCTORS |
| ARE NOT OF SUFFICIENT SIZE PER 240.21,310.16,110.14. |
| PLEASE ADJUST. |
| |
| 2) NOTE: PLEASE SEE PANEL *H* AS THIS PANEL SHOWS 3/0 |
| CONDUCTORS YET THE RISER SHOWS 1/0 TAPPED CONDUCTORS. |
| DEPENDING ON OVER CURRENT PROTECTION FOR TAPPED |
| CONDUCTORS ARE NOTED ABOVE IN NOTE #1 THIS WILLNEED |
| TO CHANGE AND COORDINATE. |
| 240.21,310.16 ETC |
| FBC 106.1.1 FOR CLARITY AND COORDINATION. |
| |
| 3) NOTE: PLEASE SEE THE NEW PANEL *S* WHICH BASED ON |
| THE PANEL SCHEDULE IT SHOWS NEW FEEDERS TO BE 4-#3 AND |
| 1#8 FOR EQUIPMENT GROUNDING HOWEVER BASED ON THE RISER |
| THE FEEDERS ARE SHOWN AS 4-#6 AND 1-#10 EQUIPMENT |
| GROUND. PANEL SCHEDULE R1 STATES #6. |
| PLEASE ALSO SEE THE PANEL IS NOTING THIS AS AN 18 |
| CIRCUIT PANEL YET THE PANEL IS SHOWN AS 42 CIRCUIT. |
| WHICH WILL BE THE FEEDERS? |
| 310.16,240.4 ETC |
| FBC 106.1.1, 106.1.2 FOR CLARITY AND COORDINATION. |
| |
| 4) NOTE: PLEASE SEE PANEL *R1* AS THE RISER SHOWS THIS |
| PANEL AS A 400AMP RATED PANEL WITH 400AMP MAIN CIRCUIT |
| BREAKER YET THE PANEL *R1* SHOWS THIS PANEL AS A 225AMP |
| RATED PANEL WITH A 200AMP MAIN. BASED ON THE LOAD ON |
| PANEL THE PANEL MAY NOT CONTAIN A 200AMP BREAKER. THE |
| LOAD EXCEEDS THE RATING OF THE 200AMP MAIN. PLEASE ALSO |
| SEE THIS SAME PANEL IS NOTED WITH 30 CIRCUITS YET |
| SCHEDULE INDICATES 42 CIRCUITS. CAN NOT BE 30 CIRCUITS |
| AS THERE ARE BRANCH CIRCUITS SHOWN ABOVE THE 30 |
| CIRCUITS ON SCHEDULE. |
| PLEASE ADJUST ALL DEVICES, PANEL RATINGS, MAINS, |
| CIRCUITS ETC. |
| 240.21,408.36, 408.4 ETC |
| FBC 106.1.1, 106.1.2 FOR CLARITY AND COORDINATION. |
| |
| 5) NOTE: PLEASE SEE PANEL *H* WHICH STILL INDICATES A |
| 150AMP SUB BRANCH BREAKER TO FEED EXISTING TRANSFORMER |
| YET THE RISER SHOWS THE TRANSFORMER NOW BEING FED FROM |
| A NEW MAIN DISCONNECT TAPPED FROM THE GUTTER. BASED ON |
| REVISED RISER THE TRANSFORMER IS NO LONGER BEING FED |
| FROM PANEL *H*. |
| 408.4 |
| FBC 106.1.1 FOR CLARITY AND COORDINATION. |
| |
| 6) NOTE: PLEASE SEE PREVIOUS COMMENTS IN REFERENCE TO |
| ROOM 1514 WHICH IS NOTED ON PLANS AS A SERVER ROOM. |
| THIS ROOM HAS SEPARATE AC EQUIPMENT, SEPARATE PANEL |
| FEEDING TWO SERVERS AND THE RESPONSE WAS THE EPO BUTTON |
| WAS REMOVED. THE PREVIOUS REVIEW NOTED STATED THAT IF |
| THIS IS NOT AN IT ROOM BY NEC 645 DEFINITIONS THEN |
| PLACE NOTE ON PLANS THAT WIRING METHODS IN NEC 645 ARE |
| NOT PERMITTED. WIRING METHODS UNDER NEC 645 ARE LESS |
| STRINGENT THAN CHAPTERS 1-4. |
| |
| 7) NOTE: PLEASE SEE PANELS R2 AND R3 ARE BOTH SHOWN AS |
| 200AMP MAIN CIRCUIT BREAKER PANELS YET THE RISER SHOWS |
| BOTH AS MAIN LUG ONLY. |
| PLEASE COORDINATE. |
| 408 |
| FBC 106.1.1 FOR CLARITY AND COORDINATION. |
| |
| 8) NOTE: PLEASE SEE THE MAIN ELECTRICAL ROOM HAS NOT |
| BEEN REVISED ON PLANS TO SHOW NEW EQUIPMENT WITH NEW |
| LOCATIONS. |
| 240.24, 110.26 |
| FBC 106.3.5.1.2, 106.1.1 |
| |
| 9) NOTE: PLEASE SEE THE FIXTURE *H* WHICH WAS MISSING |
| THE FIXTURE DESIGNATION ON PREVIOUS PLANS INDICATES THE |
| LIGHTING CONTROL CIRCUIT TO G2-2, YET THE SCHEDULE |
| SHOWN ON E-5 DOES NOT LIST THE FIXTURE *H* UNDER G2-2 |
| ONLY FIXTURES *B* AND *BE* ARE LISTED. |
| PLEASE REVISE CIRCUITING ON SCHEDULES ON SHEET E-5 AS |
| THIS IS A NEW SHEET WITH NEW CIRCUITS FOR LIGHTING |
| WHICH WAS NOT PART OF THE PREVIOUS REVIEWED PLANS. THIS |
| IS NOT THE ONLY CIRCUIT WHICH DOES NOT COORDINATE. AN |
| ADDITIONAL EXAMPLE IS CIRCUIT G2-6 AS THIS IS SHOWN AS |
| A SPARE ON SHEET E-5 YET PLEASE SEE CORRIDOR 1510 ON |
| PLANS AS FIXTURES *C* ARE CLEARLY SHOWN WITH THIS SAME |
| CIRCUIT. |
| PLEASE BE SURE TO GO OVER ALL NEW CIRCUITING AND |
| SCHEDULE.. |
| FBC 13-415.1.ABC.1.1, .1.3. |
| FBC 106.1.1.1 |
| |
| IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |