2008-06-20 13:50:33REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PLANS ARE CODE COMPLIANT. HOWEVER, THERE ARE TWO
 OUTSTANDING ISSUES WHICH SHALL BE RESOLVED PRIOR TO
 PERMIT ISSUANCE:
  
 1. PG M2.1: IT IS UNCLEAR AT THIS TIME OF SERVER ROOM
 1514 WILL BE CLASSIFIED AS AN I.T. ROOM. PLEASE SEE
 ELECTRICAL COMMENTS. A 1-HOUR RATING MAY BE REQUIRED AT
 THE WALLS OF THIS ROOM. IN THIS CASE, THE DUCT
 PENETRATIONS INTO THIS ROOM WILL NEED TO BE PROTECTED
 IN ACCORDANCE WITH FBCM 607.5.
  
 2. PG M7.1: DETAIL #5 CALLES FOR A PRE-ENGINEERED A/C
 STAND TO BE INSTALLED. THESE STANDS ARE DEFINED AS
 STRUCTURAL COMPONENTS BY FAC RULE 9B-72 AND PRODUCT
 APPROVAL IS REQUIRED. PLEASE PROVIDE PRODUCT APPROVAL
 DOCUMENTATION APPROVED IN WRITING BY THE DESIGNER OF
 RECORD IN ACCORDANCE WITH FBCB 106.3.3. FOR MORE
 INFORMATION ON THE FLORIDA PRODUCT APPROVAL SYSTEM
 PLEASE VISIT WWW.FLORIDABUILDING.ORG.
  