Plan Review Notes For Permit 08050629 |
Permit Number |
08050629 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-06-20 13:50:33 | REVIEW #: 1ST | | ACTION: DENIED | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | PLANS ARE CODE COMPLIANT. HOWEVER, THERE ARE TWO | | OUTSTANDING ISSUES WHICH SHALL BE RESOLVED PRIOR TO | | PERMIT ISSUANCE: | | | | 1. PG M2.1: IT IS UNCLEAR AT THIS TIME OF SERVER ROOM | | 1514 WILL BE CLASSIFIED AS AN I.T. ROOM. PLEASE SEE | | ELECTRICAL COMMENTS. A 1-HOUR RATING MAY BE REQUIRED AT | | THE WALLS OF THIS ROOM. IN THIS CASE, THE DUCT | | PENETRATIONS INTO THIS ROOM WILL NEED TO BE PROTECTED | | IN ACCORDANCE WITH FBCM 607.5. | | | | 2. PG M7.1: DETAIL #5 CALLES FOR A PRE-ENGINEERED A/C | | STAND TO BE INSTALLED. THESE STANDS ARE DEFINED AS | | STRUCTURAL COMPONENTS BY FAC RULE 9B-72 AND PRODUCT | | APPROVAL IS REQUIRED. PLEASE PROVIDE PRODUCT APPROVAL | | DOCUMENTATION APPROVED IN WRITING BY THE DESIGNER OF | | RECORD IN ACCORDANCE WITH FBCB 106.3.3. FOR MORE | | INFORMATION ON THE FLORIDA PRODUCT APPROVAL SYSTEM | | PLEASE VISIT WWW.FLORIDABUILDING.ORG. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|