Date |
Text |
2008-06-20 10:05:29 | ** DENIEDREVIEW ** |
| |
| |
| 1) NOTE: PLEASE VERIFY THE KEYPADS AND LOCATIONS WHICH |
| APPEAR TO BE SHOWN ON PLANS WITH A K INSIDE A SQUARE. |
| THIS REVIEWER COULD NOT LOCATE THIS ON THE SYMBOL |
| LEGEND FOR TYPE OF DEVICE. PLEASE ALSO STATE THE |
| MAXIMUM TIME FOR OVER RIDE OF THESE KEYPAD DEVICES. |
| (MAXIMUM FOUR HRS FOR TIMER TYPE DEVICES AND 30MINS FOR |
| OCCUPANCY SENSORS). |
| PLEASE SEE THE LOCATIONS FOR KEYPADS ARE REQUIRED TO BE |
| SHOWN AT ALL LOCATIONS SO THAT WHEN AN OCCUPANT IS |
| ENTERING A SPACE THE LIGHTING CAN BE CONTROLLED AND THE |
| OCCUPANT CAN VISUALLY SEE ALL LIGHTING WHICH IS BEING |
| CONTROLLED.IF THE OCCUPANT CAN NOT VISUALLY SEE AL |
| LIGHTING WHICH IS BEING CONTROLLED THEN DEVICES SUCH AS |
| PILOT LIGHTS ARE REQUIRED AND WOULD NEED TO BE SHOWN ON |
| PLANS. |
| THERE IS A NOTE ON PLANS ON SHEET E-3 ON UPPER RIGHT |
| HAND SIDE OF FLOOR LAYOUT WHICH STATES THE LOCATIONS OF |
| KEYPADS ARE TO BE VERIFIED WITH ARCHITECT. THE |
| LOCATIONS MAY BE VERIFIED WITH ARCHITECT HOWEVER THE |
| MINIMUM LOCATIONS PER CODE NEED TO BE DETERMINED AND |
| SHOWN ON PLANS. |
| PLEASE SEE ONE LOCATION FOR EXAMPLE WHICH APPEARS TO BE |
| IN THE RECEPTION AREA WHERE THE ASSUMED KEYPAD IS |
| LOCATED INSIDE AND AROUND THE CORNER. |
| IF ZONES ARE IN DESIGN PLEASE SHOW ZONES FOR ASSUMED |
| KEYPADS. IF ALL COMMON AREA LIGHTING IS GOING TO BE |
| CONTROLLED FROM ALL KEYPAD LOCATIONS AS NOTED ABOVE |
| PILOT LIGHT CONTROL PANELS WITH ALL AREA DESIGNATIONS |
| ARE REQUIRED. |
| 13-415.1.ABC.1.1, .1.2. |
| |
| 2) NOTE: PLEASE SUBMIT SCHEDULING, AND INFORMATION ON |
| PROPOSED LIGHTING CONTROLLED PANEL. PLANS SHOW A |
| LIGHTING CONTROL PANEL HOWEVER NO OTHER INFORMATION FOR |
| DEVICES ETC AS NOTED ABOVE IS SHOWN. |
| 13-415.1.ABC.1, NEC 110.3, 90.7 |
| FBC 106.1.2 FOR ADDITIONAL INFORMATION AND |
| COORDINATION. |
| |
| 3) NOTE: PLEASE SEE 13-415.1.ABC.1.3 FOR REQUIRED |
| ADDITIONAL CONTROLS. |
| CONTROLS ARE REQUIRED IN THE FOLLOWING CASES: 1.DISPLAY |
| OR ACCENT LIGHTING. DISPLAY OR ACCENT LIGHTING SHALL |
| HAVE A SEPARATE CONTROL. |
| |
| 4) NOTE: PLEASE LABEL THE FIXTURES SHOWN IN WAITING |
| RECEPTION AREA 1502 WHICH ARE SHOWN DIAGONALLY ACROSS |
| THE CEILING AREA. NO FIXTURE DESIGNATION COULD BE |
| LOCATED AT OR NEAR THESE FIXTURES AND COMPLIANCE WITH |
| LIGHTING CONTROLS ABOVE, LIGHTING PERFORMANCE |
| CALCULATIONS AND LIGHTING FIXTURE LEGEND NEED TO BE |
| VERIFIED. |
| 13-415.2.ABC.1.1, .1.2, 13-415.2, 13-415.1.ABC.1.3. |
| |
| 5) NOTE: PLEASE STATE AND SHOW THE MINIMUM LEVELS FOR |
| ADA COMPLIANCE FOR HORN AND STROBE LEVELS. |
| PLEASE SEE FBC 11-4.28.1, .2 AND .3(4). |
| |
| 6) NOTE: PLEASE SEE PLANS WHICH APPEAR TO BE SHOWING AN |
| EPO EMERGENCY POWER OFF BUTTON AT SERVER ROOM DOOR. |
| PLANS ALTHOUGH DO NOT APPEAR TO BE SHOWING A ONE HOUR |
| WALL AROUND ROOM BASED ON ARCHITECTURAL PLANS. BASED ON |
| THE ROOM AS SHOWN NOT FALLING UNDER AN IT ROOM PER |
| 645.2 DEFINITIONS PLEASE PLACE A NOTE ON ELECTRICAL |
| PLANS WHICH NEEDS TO STATE * ALL WIRING METHODS SHALL |
| MEET CHAPTERS 1-4* WIRING METHODS IN 645 ARE NOT |
| PERMITTED. |
| |
| ** IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| HESITATE IN CONTACTING THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |