2008-06-20 11:07:43BUILDING PLAN REVIEW
 PERMIT: 08050629
 ADD: 777 S. FLAGLER DRIVE SUITE 1500
 CONT: BUTLER CONSTRUCTION
 TEL: (561)832-9700
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 6-19-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4)2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 5)THE DOOR SCHEDULE HAS CONFLICTING INFORMATION WHEN
 REFERRING TO THE DOOR TYPES EXAMPLE, DOOR #1510; THE
 DOOR SCHEDULE INDICATETYPE (C)AS A SOLID WOOD
 SINGLE DOOR ACCORDING TO THE DOOR TYPES, HOWEVER THE
 MATERIAL IS NOTED AS GLASS ON THE SCHEDULE. PLEASE NOTE
 THERE IS NO TYPE (A2) DOOR SHOWN ON SHEET A-1.0,
 HOWEVER IT IS INDICATED IN THE DOOR SCHEDULE.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED. 106.1.1.
  
 6)INDICATE HOW THE METAL TRACK OR ANY MATERIAL WILL
 BE FASTENED TO THE STRUCTURE ABOVE. THE DETAIL SHEETS
 SHALL STATE THE TYPE OF FASTENERS TO BE USED. THERE IS
 NO INDICATION AS TO WHAT TYPE OF FASTENERS WILL BE
 USED.
 7)FBC 603. DUE TO THE FACT THAT THIS IS A TYPE I
 BUILDING THE FURRING AND BACKING MATERIALS SHALL BE
 FIRE-RETARDANT-WOOD WHICH IS NOT STATED ON SOME OF THE
 DETAIL SHEETS. INTERIOR FINISH MATERIALS ARE REQUIRED
 TO BE APPLIED DIRECTLY TO EXPOSED SURFACES OF
 STRUCTURAL ELEMENTS OR TO FURRING STRIPS NOT EXCEEDING
 1.75 INCHES ATTACHED TO SUCH SURFACES. FBC 803.4.1.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
2008-06-19 15:50:45REVIEW IN PROGRESS