2008-06-20 11:07:43 | BUILDING PLAN REVIEW |
| PERMIT: 08050629 |
| ADD: 777 S. FLAGLER DRIVE SUITE 1500 |
| CONT: BUTLER CONSTRUCTION |
| TEL: (561)832-9700 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 6-19-08 |
| REVIEW: 1ST |
| ACTION: DENIED |
| |
| 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE 2007 SUPPLEMENTS. |
| |
| 4)2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN |
| OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| THIS CODE. |
| |
| 5)THE DOOR SCHEDULE HAS CONFLICTING INFORMATION WHEN |
| REFERRING TO THE DOOR TYPES EXAMPLE, DOOR #1510; THE |
| DOOR SCHEDULE INDICATETYPE (C)AS A SOLID WOOD |
| SINGLE DOOR ACCORDING TO THE DOOR TYPES, HOWEVER THE |
| MATERIAL IS NOTED AS GLASS ON THE SCHEDULE. PLEASE NOTE |
| THERE IS NO TYPE (A2) DOOR SHOWN ON SHEET A-1.0, |
| HOWEVER IT IS INDICATED IN THE DOOR SCHEDULE. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED. 106.1.1. |
| |
| 6)INDICATE HOW THE METAL TRACK OR ANY MATERIAL WILL |
| BE FASTENED TO THE STRUCTURE ABOVE. THE DETAIL SHEETS |
| SHALL STATE THE TYPE OF FASTENERS TO BE USED. THERE IS |
| NO INDICATION AS TO WHAT TYPE OF FASTENERS WILL BE |
| USED. |
| 7)FBC 603. DUE TO THE FACT THAT THIS IS A TYPE I |
| BUILDING THE FURRING AND BACKING MATERIALS SHALL BE |
| FIRE-RETARDANT-WOOD WHICH IS NOT STATED ON SOME OF THE |
| DETAIL SHEETS. INTERIOR FINISH MATERIALS ARE REQUIRED |
| TO BE APPLIED DIRECTLY TO EXPOSED SURFACES OF |
| STRUCTURAL ELEMENTS OR TO FURRING STRIPS NOT EXCEEDING |
| 1.75 INCHES ATTACHED TO SUCH SURFACES. FBC 803.4.1. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |