2008-06-20 16:36:48 | *****DENIED***** |
| |
| |
| 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| |
| 02.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| SHALL BE REMOVED FORM THE SITE AT THE END OF EACH SHIFT |
| OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| |
| 03.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE |
| EMERGENCY RESPONSE TO THE SAID PROPERTY OR THE VICINITY |
| THEREOF (INCLUDING STREETS, ALLEYS, FIRE LANES, ETC.) |
| . |
| |
| 04.ON SHEET A-1, WHAT IS THE DOOR NUMBER IS SCHEDULED |
| FOR THE ROOM CONTAINING THE AIR HANDLER UNIT (A.H.U.) |
| ? |
| |
| 05.ON SHEET A-2, ROOM DOOR 215 LOCATED BETWEEN THE |
| ELEVATOR AND THE FOYER IS LISTED AS LIVING ROOM. PLEASE |
| EXPLAIN. |
| |
| 06.ON SHEET A-2, ROOM DOOR 212 IS LISTED IN THE DOOR |
| SCHEDULE AS BATHROOM. |
| |
| 07.ON SHEET E-1 & E-2, REFERENCES ARE MADE TO SMOKE |
| DETECTORS BEING USED IN THE DWELLING UNITS.PLEASE BE |
| ADVISED THAT MOKE DETECTORS (SD) ARE TIED INTO A |
| BUILDING'S FIRE ALARM SYSTEM, WHEREAS SMOKE ALARMS |
| SOUND ONLY WITHIN AN INDIVIDUAL DWELLING UNIT AND SHALL |
| NOT ACTUATE THE BUILDING FIRE ALARM SYSTEM. |
| |
| 08.PROVIDE PRESCRIPTIVE STRENGHTS FOR THE STAIR |
| HANDRAILS/GUARDRAILS. |
| |
| 09.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| REFERENCED. |
| |
| 10.30.1.2.2- NO DWELLING UNIT OF A RESIDENTIAL |
| OCCUPANCY SHALL HAVE ITS SOLE MEANS OF EGRESS PASS |
| THROUGH ANY NONRESIDENTIAL OCCUPANCY IN THE SAME |
| BUILDING. |
| |
| 11.30.1.2.3- THE SEPARATION OF THE DWELLING UNITS |
| OF THE RESIDENTIAL OCCUPANCY AND EXITS FROM THE |
| NONRESIDENTIAL OCCUPANCY SHALL BE BY CONSTRUCTION |
| HAVING A FIRE RESISTAIVE RATING OF NOT LESS THAN 1 |
| HOUR. |
| |
| 12.30.3.3.2- SPECIFY THE INTERIOR FINISH FOR THE |
| EXIT ENCLOSURE, LOBBIES AND CORRIDORS, AND OTHER SPACES |
| IN TERMS OF CLASS A, CLASS B, OR CLASS C. |
| |
| 13.30.3.5.11 - SHOW THE LOCATION OF THE 2A10 BC RATED |
| FIRE EXTINGUISHERS WHICH SATIFISFY THE 75' TRAVEL |
| DISTANCE. |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET |
| EACH COMMENT WAS ADDRESSED. |
| |
| |
| CAPT. MICHAEL A. WILLIAMS |
| FIRE PLAN REVIEW |
| 561-805-6722 |
| |
| |
| |
| |
| |
| |