Plan Review Notes
Plan Review Notes For Permit 08050627
Permit Number 08050627
Review Stop E
Sequence Number 1
Notes
Date Text
2008-06-19 12:34:43** DENIEDREVIEW **
  
  
 1) NOTE:PLEASE SEE THAT PLANS AND DOCUMENTS NEEDED TO
 BE SUBMITTED ARE NOT COMPLETE AT THIS TIME. THERE MAY
 VERY WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 CAN NOT BE MADE AT THIS TIME DUE TO LACK OF INFORMATION
 AND CODE COMPLIANCE.
  
 2) NOTE: PLEASE SEE ATTACHED PRINT OUT FROM THE
 DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION.AT
 THE TIME OF THIS REVIEW THE PRINT OUT INDICATES THE
 ARCHITECT OF RECORD AS SIGNED, DATED AND SEALED ON
 PLANS LICENSE WAS SUSPENDED IN JULY 2007. THIS LICENSE
 IS NOT CURRENT AS SHOWN BY THE STATE AND PLANS MAY NOT
 BE SIGNED, DATED AND SEALED BY THIS ARCHITECT AS
 SHOWN.
 ** CONTACT HAS BEEN MADE TO THE BOARD OF ARCHITECTS
 LEGAL COUNSEL TO VERIFY THE STATE WEBSITE INFORMATION
 AS SHOWN IS ACCURATE.
  
 3) NOTE: PLEASE BE SURE TO COMPLETE ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULES.
 PLEASE SEE MOST OF DEVICES WHICH DO NOT INDICATE ANY
 CIRCUITS AND MANY CIRCUITS WHICH DO NOT CORRELATE WITH
 THE SUBMITTED SCHEDULES. THERE ARE SEVERAL CODES WHICH
 MINIMUM CIRCUITING CAN NOT BE VERIFIED FOR CODE
 COMPLIANCE AT THIS TIME.
 FBC ADMIN SECTION 106.3.5.1.2, 106.5.4
 NEC 408.4, 240.4, 310.16, 210.52, 210.11 ETC
  
 4) NOTE: PLEASE BE SURE PLANS REFERENCE THE CURRENT
 CODES IN EFFECT AS LISTED.
 NFPA-101 2003, NFPA-72 2002, NFPA-70 2005, AND 2004 FBC
 W/ 2007 REVISIONS.
  
 5) NOTE: PLEASE SUBMIT COMPLETED ENERGY CALCULATIONS
 FOR ALL AREAS WHICH ARE APPLICABLE FOR USE AND
 OCCUPANCY. PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2
 AND .1.3 FOR LIGHTING PERFORMANCE CALCULATIONS. PLEASE
 SEE 13-400.3.A, 13-400.3.B, 13-400.3.C, 13-101.3. AS
 THE MINIMUM REQUIRED CALCULATIONS WERE NOT SUBMITTED
 MINIMUM CODE COMPLIANCE HAS NOT BEEN MET OR VERIFIED.
  
 6) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AS THE FOLLOWING
 WORDING IS REQUIRED TO BE ON PLANS.
 CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT WITHIN 30
 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD
 DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDED
 TO THE BUILDING OWNER, INCLUDING:13-413.1.ABC.2.2
 MANUALS.
 CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT AN OPERATING
 MANUAL AND MAINTENANCE MANUAL BE PROVIDED TO THE
 BUILDING OWNER. THE MANUALS SHALL INCLUDE, AT A
 MINIMUM, THE FOLLOWING:
 1. SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED
 OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING
 MAINTENANCE.
 2. OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH
 PIECE OF EQUIPMENT REQUIRING MAINTENANCE. REQUIRED
 ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY
 IDENTIFIED.
 3. NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED
 SERVICE AGENCY.
 NOTE: ENFORCEMENT AGENCIES SHOULD ONLY CHECK TO BE SURE
 THAT THE CONSTRUCTION DOCUMENTS REQUIRE THIS
 INFORMATION TO BE TRANSMITTED TO THE OWNER AND SHOULD
 NOT EXPECT COPIES OF ANY OF THE MATERIALS.
 SOME TEXT ABOVE WAS TAKEN DIRECTLY FROM THE FBC FOR
 EASE OF CORRECT WORDING REQUIRED ON PLANS.
  
 7) NOTE: PLEASE SEE THE RISER SUBMITTED IS NOT COMPLETE
 AT THIS TIME. PLEASE SEE NO MAINS, NO OVER CURRENT
 PROTECTION FOR PANELS, MAINS ETC WERE SUBMITTED OR
 SHOWN.
 PLEASE SUBMIT A COMPLETE RISER DIAGRAM MEETING MINIMUM
 CODE COMPLIANCE FOR SERVICES. 230.70,230.71,230.72,
 215.5, 310.16, 240.4 ETC
 **
 8) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR TO EACH PANEL.
 250.110,250.122, 250.24 ETC.
  
 9) NOTE: PLEASE SEE GROUNDING ELECTRODE SYSTEM MENTIONS
 TO ATTACH TO FOOTER STEEL? PLEASE KNOW IN AN EXISTING
 BUILDING, IT IS NOT REQUIRED AND IS NOT RECOMMENDED DUE
 TO THE STRUCTURAL INTEGRITY OF THE EXISTING
 STEEL/FOOTER.
 PLEASE KNOW HOWEVER THIS IS PERMITTED AND IF SHOWN ON
 RISER, IT WILL BE REQUIRED.
 250.50
  
 10) NOTE: PLEASE SEE 250.66 FOR SIZING OF GROUNDING
 ELECTRODE CONDUCTOR AS THIS IS CURRENTLY SHOWN AS A
 "6/0"? PLEASE KNOW THIS IS NOT A RECOGNIZED STANDARD IN
 THE NATIONAL ELECTRICAL CODE OR THE AMERICAN WIRE GAUGE
 STANDARD. PLEASE ADJUST AS NEED BASED ON SERVICE
 ENTRANCE CONDUCTORS WHICH WILL BE BASED ON LOAD
 CALCULATIONS.PLEASE BE SURE TO SEE COMMENTS BELOW FOR
 MINIMUM SERVICE ENTRANCE CONDUCTORS TO VERIFY.
  
 11) NOTE: PLEASE SEE NOTE WITH RESPECT TO LOAD
 CALCULATIONS. AS THE SUBMITTED CALCULATIONS DO NOT
 MINIMUM CODE COMPLIANCE THE SIZE OF THE EXISTING
 SERVICE ENTRANCE CONDUCTORS AS SHOWN ON RISER CAN NOT
 BE VERIFIED.
  
 10) NOTE: PLEASE SUBMIT AIC RATINGS FOR ALL NEW SERVICE
 EQUIPMENT BEING INSTALLED. PLEASE SEE 110.9 AS MAINS,
 BREAKERS AND ALL SERVICE EQUIPMENT IS REQUIRED TO RATED
 FOR THE AVAILABLE FAULT CURRENT.
 PLEASE SEE NOTE #20 AS LISTED ON E-2 WHICH MENTIONS TO
 USE FUSES HOWEVER AS NO INFORMATION IS SHOWN ON RISER
 FOR ANY MAINS, SERVICE EQUIPMENT ETC THESE CAN NOT BE
 VERIFIED.
  
 12) NOTE: PLEASE SHOW LOAD CALCULATIONS MEETING THE
 2005 NEC> PLEASE SEE THE CODE SECTIONS REFLECTED ON
 PLANS ARE NOT FROM THE 2005 NATIONAL ELECTRICAL CODE.
 PLEASE SEE THE COMMERCIAL PORTION OF THE BUILDING
 ACTUALLY SHOWS *RESIDENTIAL* LOAD CALCULATIONS. HOW IS
 THIS POSSIBLE? WHERE IN THE NEC DOES IT PERMIT
 RESIDENTIAL LOAD CALCULATIONS IN COMMERCIAL OFFICE
 SPACE?
 PLEASE SEE 220.12, 220.14, 220.42, 220.43, ETC. PLEASE
 BE SURE TO SHOW ALL CONTINUOUS LOADS AT 125% PER 215.3,
 230.42 ETC.
 AS CALCULATIONS ARE NOT COMPLETE AND THERE IS MUCH NEED
 FOR COORDINATION PLEASE KNOW NEW COMMENTS MAY ARISE
 ONCE THESE ARE RESUBMITTED.
  
 13) NOTE: PLEASE SEE COMMON AREAS ON PLANS WILL REQUIRE
 SOME SORT OF *HOUSE/COMMON* ARE PANEL. THESE CIRCUITS
 IN THESE AREAS MAY NOT BE FED FROM THE APARTMENT UNITS
 OR COMMERCIAL TENANT SPACE.
 210.25 ETC. AS MOST OF THE CIRCUITING IS NOT SHOWN MOST
 ITEMS CAN NOT BE VERIFIED FOR MINIMUM CODE COMPLIANCE.
  
 14) NOTE: PLEASE SHOW ALL PANEL LOCATIONS FOR
 VERIFICATION OF CODE COMPLIANCE.
 110.26,240.24 ETC.
 FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION
 AND COORDINATION.
  
 15) NOTE: PLEASE CORRELATE ALL LOAD FOR A/C SYSTEMS, AS
 MECHANICAL PLANS INDICATE 10KW UNITS, LOAD
 CALCULATIONS
 INDICATE BOTH 9KW LOAD AND 5KW LOAD AND PANEL SCHEDULES
 INDICATE 5KW HEAT FOR ALL??
 PLEASE ADJUST LOAD CALCULATIONS AND COORDINATE OTHER
 COMMENTS.
  
 16) NOTE: PLEASE SEE 424.3B WHICH REQUIRES ALL MINIMUM
 OVER CURRENT PROTECTION FOR AIR HANDLER UNIT HEAT TO BE
 SIZED AT A MINIMUM OF 125%.
 PLEASE SEE PANEL SCHEDULES SHOWS 50A, #6 AWG ON 5KW
 UNITS.
  
 17) NOTE: PLEASE SEE CONDUCTORS SHOWN FOR RANGE/OVENS
 WHICH DO NOT SHOW ANY NEUTRAL CONDUCTOR AS REQUIRED PER
 250.140
  
 18) NOTE: PLEASE SEE MISSING MINIMUM DISCONNECTS FOR
 ALL AIR CONDITIONING EQUIPMENT. AS NOT ALL EQUIPMENT IS
 CURRENTLY SHOWN PLEASE BE SURE TO SEE 440.11 AND 110.26
 AND SHOW LOCATIONS OF ALL REQUIRED DISCONNECTS.
  
 19) NOTE: PLEASE SEE MISSING REQUIRED GFI SERVICE
 RECEPTACLE FOR OUTSIDE CONDENSING UNITS.210.63,
 210.8A3, 210.8B4.
  
 20) NOTE: PLEASE SEE AN ELEVATOR IS SHOWN ON PLANS,
 HOWEVER THERE IS NO INDICATION ON ANY PLANS OF THIS
 EQUIPMENT OR EQUIPMENT ROOM.
 PLEASE SHOW LOCATION OF EQUIPMENT.
 PLEASE SEE 620.23, 620.24 FOR MISSING REQUIRED
 DEDICATED CIRCUITS. PLEASE SEE SAME SECTIONS AS
 RECEPTACLE SHALL BE GFI PROTECTED.
 PLEASE SEE 700.16 FOR MISSING BACK UP LIGHT DEPENDING
 ON LOCATION OF EQUIPMENT.
  
 21) NOTE: PLEASE SEE 13-415.1.ABC.1.4 FOR REQUIRED
 CONTROL OF OUTSIDE LIGHT. SOME LIGHTS NOTE TO BE
 CIRCUITED TO A TC (ASSUMING TIME CLOCK) HOWEVER PLEASE
 SEE CURRENT CODE SECTION GIVEN AS A STANDARD TIME CLOCK
 IS NOT ACCEPTABLE.
 PLEASE PROVIDE ONE OF TWO ACCEPTABLE METHODS AND
 INDICATE ON PLANS.
 PLEASE BE SURE TO SEE NOTES ABOVE WITH RESPECT TO
 COMMON AREAS WHICH OUTSIDE LIGHTING WOULD BE TO NEW
 HOUSE PANEL ETC.
  
 22) NOTE: PLEASE SEE THE MISSING REQUIRED DEDICATED
 SIGN CIRCUIT AS PER 600.5
  
 23) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR
 MINIMUM LIGHTING LEVELS UNDER THE 2003 NFPA-101 LIFE
 SAFETY CODE FOR EGRESS PATHS AND STAIRS.
 PLEASE SEE 7.8.1.3, 7.9.2.2.
 PLEASE KNOW AS THESE ARE COMMON AREAS, CONTROLS AND
 CIRCUITING NEED TO BE ADJUSTED ACCORDING.
  
 24) NOTE: PLEASE SEE PLANS SHOW SD FOR SMOKE DETECTORS
 AS DEFINED IN NFAP-72. IF THESE ARE TRULY SMOKE
 DETECTORS WHICH ONLY DETECT AND DO NOT SOUND AN ALARM
 PLEASE SUBMIT THE COMPLETE FIRE ALARM SYSTEM INCLUDING
 HORNS, FIRE ALARM PANEL ETC.
 PLEASE SEE THE COMMON AREAS MAY NOT HAVE THE
 RESIDENTIAL UNITS SMOKE ALARMS DEVICES WIRED INLINE OR
 SAME CIRCUITS.
 PLEASE ADJUST.
 PLEASE SEE THE DEFINITIONS FOR SMOKE ALARMS AND SMOKE
 DETECTORS AND ADJUST DESIGN ACCORDINGLY.
  
 25) NOTE: PLEASE PROVIDE A FIXTURE LEGEND/SCHEDULE AND
 CORRELATE WITH THE PLANS. PLEASE BE SURE THE FIXTURE
 LEGEND IS COMPLETE FOR ALL COMMON AREAS AND OFFICE
 AREAS. PLEASE INCLUDE AREAS FOR RESIDENTIAL ALSO WITH
 RESPECT TO THE RECESSED LIGHTING FIXTURES.
 13-415.2.ABC.1, 13-415.2 FOR COMMERCIAL,
 13-606.1.ABC.1.2.4 FOR RESIDENTIAL.
  
 26)NOTE: PLEASE BE SURE TO SEE 700.12F FOR CIRCUITING
 OF REQUIRED EMERGENCY AND EXIT LIGHT FIXTURES.
  
 27) NOTE: PLEASE SEE 210.8A2WHICH REQUIRES A;;
 RECEPTACLES IN BATHROOMS TO BE SHOWN AS GFI/GFI
 PROTECTED. SOME ARE AND SOME ARE NTO.
  
 28) NOTE: PLEASE SEE 210.52D, 210.11C3 FOR MISSING
 REQUIRED DEDICATES BATH CIRCUITS. MUST BE 20AMP AND #12
 MINIMUM.
  
 29) NOTE: PLEASE SEE NFPA-72 11.8.3 FOR LOCATIONS AND
 TYPES OF SMOKE DETECTION DEVICES WITHIN 20FT OF COOKING
 APPLIANCES.
 PLEASE ALSO SEE NOTE ON PLANS WHICH MENTIONS SMOKE
 DETECTORS ARE TO BE WIRED AHEAD OF THE SWITCHES ON
 EITHER BATH OR KITCHEN LIGHTING CIRCUIT, PLEASE SEE
 THIS IS OK, HOWEVER ARC FAULT PROTECTION WILL THEN BE
 REQUIRED FOR THOSE LIGHTING CIRCUITS.
 210.12 NEC
  
 31) NOTE: PLEASE LIST ALL THE REQUIRED ARC FAULT
 PROTECTED CIRCUITS AS REQUIRED PER 2005 NEC 210.12B.
 PLEASE SEE COMMENTS ABOVE AS THE CIRCUITS SHALL BE
 SPECIFIC AND AS OTHER COMMENTS HAVE AFFECTED DEDICATED
 CIRCUITS PER NOTES PLEASE BE SURE TO COORDINATE.
  
 32) NOTE: PLEASE BE SURE TO SEE 220.52, 210.52B1 FOR
 DINING ROOM/AREA CIRCUITING.
  
 33) NOTE: PLEASE SEE MANY CIRCUITS ON PLANS MENTIONS
 *GENERAL LIGHTS* AND GENERAL RECEPTACLES*.
 PLEASE SEE 408.4 AS ALL CIRCUITING SHALL BE SPECIFIC TO
 ROOMS AND AREAS IN WHICH THEY FEED.
 FBC 106.1.2, 106.3.5.1.2, 106.3.5.4
  
 34) NOTE: PLEASE BE SURE TO LABEL APARTMENT UNITS ON
 ELECTRICAL PLANS. *A*, *B* ETC
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
 REVIEW FOR CIRCUITING WILL NEED TO BE DONE.
  
 35) NOTE: PLEASE SEE 422.30, 422.31 FOR MISSING
 DISCONNECTS FOR WATER HEATERS.
  
 36) NOTE: PLEASE SEE 210.52 FOR MISSING RECEPTACLES.
 (REDLINED ON ONE SET OF PLANS.
  
 37) NOTE: PLEASE SEE PLANS FOR OFFICE WHICH SHOWS A
 CIRCUIT FOR WHAT IS LISTED ON PANEL SCHEDULE AS BEING A
 MICROWAVE # 14, HOWEVER NO DEVICE OR LOCATION IS SHOWN
 ON PLANS.
  
 38) NOTE: PLEASE SEE SWITCHES WHICH ARE SHOWN WIRED TO
 A 3-WAY SYSTEM ON STAIRS, HOWEVER DO NOT INDICATE BEING
 S3.
 PLEASE SEE MINIMUM LIGHTING CONTROLS FOR EGRESS
 LIGHTING IN FBC CHAPTER 10 AND NFPA-1017.8
 PLEASE SEE OTHER AREAS OF PLANS IN WHICH 3-WAY
 SWITCHING IS SHOWN HOWEVER THE 3-WAY SWITCH IS ONLY
 SHOWN AT ONE END WHEN IT MUST BE AT MORE THAN ONE
 LOCATION.
  
 39) NOTE: PLEASE SEE THE ELECTRICAL PLANS AS THE PLANS
 ARE MISSING 210.63, 210.70 COMPLIANCE FOR AIR HANDLING
 UNITS.
 AS THESE WERE NOT SHOWN ON ELECTRICAL PLANS THE
 MECHANICAL PLANS WERE LOOKED AT HOWEVER THIS BECAME
 MORE CONFUSING AS PACKAGE UNITS AND SPILT SYSTEMS WERE
 SHOWN.
 IF THESE UNITS ARE PACKAGE UNITS ON ROOF, THEN WHY ARE
 THERE CONDENSING UNITS SHOWN ON THE GROUND FLOOR
 OUTSIDE LEVEL?
 IT IS UNCLEAR WHAT THE DESIGN IS GOING TO BE AS SPILT
 SYSTEMS ARE ALSO LISTED ON EQUIPMENT SCHEDULE. PLEASE
 COORDINATE ALL AND SEE NOTES ABOVE WITH RESPECT TO
 MISSING DISCONNECTS, COORDINATION OF HEAT STRIPS, OVER
 CURRENT PROTECTIONS, GFI RECEPTACLES, LIGHTS ETC.
  
 40) NOTE: PLEASE SEE MISSING GFI DESIGNATIONS FOR
 GARAGE RECEPTACLES.
 210.8A2, 5
  
 41) NOTE: PLEASE SEE MISSING CONTROL FOR EXHAUST FAN ON
 FIRST FLOOR BATHROOM.
 FBC 106.1.2
  
 42) NOTE: PLEASE SEE ELECTRICAL RISER CLEARLY STATES
 THE FEEDERS AS NOTED WILL BE TYPICAL OF *FOUR* (4) YET
 THE PLANS ONLY SHOW THREE SPACES, THREE PANELS ETC.
 PLEASE CLEAR THIS UP AND COORDINATE.
  
 43) NOTE: BASED ON COMMENTS ABOVE ONE SET OF PLANS ARE
 BEING RETAINED BY THIS OFFICE.
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]