2008-06-17 15:58:16 | BUILDING PLAN REVIEW |
| PERMIT: 08050627 |
| ADD: 421 24TH ST |
| CONT: ALONSO & ASSOCIATES, INC. |
| TEL: (561)253-5350 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| WEST PALM BEACH ADMINISTRATIVE CODE. |
| |
| 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE |
| CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE |
| CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR |
| ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 1D ) INFORMATIONAL FL S S 713.13NOTICE OF |
| COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. |
| NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS |
| AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| INSPECTION. |
| |
| 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS, |
| PLEASE UPDATE PLANS TO REFLECT THE CURRENT 2007 |
| SUPPLEMENTSAND CORRECTED WIND SPEED OF 140 MPH 3 SECOND |
| WIND GUST. NOTE AS-1 ONLY NEEDS TO UPDATE TO THE 2007 |
| SUPPLEMENTS, A-8 MAKES REFRENECE TO THE 2001 FBC |
| NUMEROUS TIMES, ALSO TO THE SOUTH FLORIDA BUILDING |
| CODE, ASCE -7-98, ASCE7-88. |
| |
| 2) PLEASE PROVIDE 2 ORIGINAL SOILS REPORTS SIGNED AND |
| SEALED.1802.2.1 QUESTIONABLE SOIL. WHERE THE |
| SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE |
| A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE |
| THAT THE NECESSARY INVESTIGATION BE MADE. SUCH |
| INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF |
| SECTIONS 1802.4 THROUGH 1802.6 . |
| |
| 3)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 4) SHEET A-1 & A-2INDICATE A ELEVATOR WITH THE EGRESS |
| STAIRS SURROUNDING THE ELEVATOR ON THREE OF THE FOUR |
| SIDES, WHICH IS LOCATED WITHIN THE VERTICAL EXIT. |
| |
| 1019.1 INDICATES AN EXIT ENCLOSURE SHALL NOT BE USED |
| FOR ANY PURPOSE OTHER THAN MEANS OF EGRESS.1019.1.1 |
| OPENINGS INTO EXIT ENCLOSURES SHALL BE LIMITED TO THOSE |
| NECESSARY FOR THE EXIT ACCESS TO THE ENCLOSURE FROM |
| FORMALLY OCCIED SPACES ANDFOR EGRESS FROM THE |
| ENCLOSRE, NOT TO COMMUNICATE AS A CORRIDOR BETWEEN |
| OFFICES. |
| |
| THE SECOND ISSUE WITH THE FIRST FLOOR DESIGN IS THE |
| CORRIDOR WHICH IS WITHIN THE VERTICAL EXIT IS A |
| HORIZONTAL EXTENSIONOF THE VERTICAL EXIT OR A EXIT |
| PASSAGE WAY. PLEASE SEE 1020.4 ELEVATORS SHALL NOT OPEN |
| INTO AN EXIT PASSAGEWAY. |
| |
| 5) A-1 THE WALL COMMON TO THE STORAGE ROOM AND THE |
| VERTICAL EXIT IS MISSING THE UL FASSEMBLY NUMBER |
| 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| |
| 6) SHEET A-1 THE BREAK AREA INDICATES A SIDE APPROACH |
| TO THE SINK, PLEASE SEE 11-4.24.2 HEIGHT. SINKS SHALL |
| BE MOUNTED WITH THE COUNTER OR RIM NO HIGHER THAN 34" |
| ABOVE THE FINISH FLOOR. |
| 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30" |
| WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS. |
| 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT |
| LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) |
| COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN |
| FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR |
| FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL |
| EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE |
| SINK. |
| |
| 7) SHEET A1 & A-4 BOTH INDICATE THE LOWER ROOF LINE |
| ENCROACHES 1'-6" OVER THE PROPERTY LINE, PLEASE REVIEW |
| 3202.3.2 FOR ALLOWABLE PROJECTIONS INTO THE RIGHT OF |
| WAY. |
| |
| 8) SHEET A-7 WINDOW DETAIL B USE OF WOOD BUCKS, PLANS |
| INDICATE THE WOOD BUCK BEVELED AND CUT SHORT OFTHE BACK |
| HALF OF THE FRAME, 1714.5.4.2 BUCKS SHALL EXTEND BEYOND |
| THE INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT |
| FULL SUPPORT OF THE FRAME IS PROVIDED. |
| |
| 9) SHEET A-6 TYPICAL WALL SECTION A,PLANS DOES NOT |
| INDICATE ON THE KNEE WALL THAT SUPPORT THE SLOPED |
| TRUSSES WHAT TYPE OF INSULATION THIS WILL BE? PLEASE |
| PROVIDE PRODUCT APPRVAL OR TESTING REPORT FOR THE |
| ICYNNE INSULATION THAT WILL BE INSTALLED IN THE |
| TRUSSES. |
| |
| 10) SHEET A-7 THE TENNANT SEPERATION WALL WILL NEED TO |
| COMPLY WITH 1207.2 AIR-BORNE SOUND TRANSIMTION OF NOT |
| LESS THAN 50 STC. |
| |
| 11) SHEET A-7 STRUCTURE -BORNE SOUND FLOOR/ CEILING |
| ASSEMBLIES BETWEEN DWELLING UNITS AND OR PUBLIC OR |
| SERVICE AREASW WITHIN THE STRUCTURE SHALL HAVE A STC |
| RATING OF NOT LESS THAN 50. |
| |
| 12) SHEET A-8 WIRE LATH NOTE INDICATES COMPLIANCE WITH |
| THE SOUTH FLORIDA BUILDING CODE, PLEASE UPDATE TO FBC |
| 2510.3- ASTM C 1063. |
| |
| 13) SHEET A-8 HANDRAIL DETAIL, THE HANDRAIL SHALL |
| EXTEND 11" BEYOND THE LAST RISER, 1009.11.5. |
| |
| 14) AC-2 ROOFTOP UNITS WITH CURBS DO NOT INDICATE HOW |
| THEY WILL BE ATTACHED TO THE ROOF DECK, PLANS ALSO SEE |
| STRUCTURAL FRAMING FOR SUPPORT FRAMING, STRUCTURAL |
| PLAANS DO NOT INDICATE ANY ADDITIONAL SUPPORT, 106.1.2 |
| ADDITIONAL INFORMATION REQUIRED. |
| |
| 15) PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO |
| COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| INFORMATION PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT. |
| WWW.FLORIDABUILDING.ORG |
| |
| 16) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 17) PGT CASEMENT WINDOWS- PLEASE PROVIDE DOCUMENTATION |
| ON THE CLEAR WIDTH OF THE WINDOWS, FROM THE PRODUCT |
| APPROVAL THE 26.5 INCH CASEMENT WINDOW WILL END UP WITH |
| LESS THAN 20 INCHES CLEAR, 1025.2.1 REQUIRES A MINIMUM |
| CLEAR OPENING OF 20" FOR EGRESS WINDOWS. |
| |
| 18) GAF BUILT UP ROOF SYSTEM: PLEASE INDICATE WHICH |
| SUB-SYSTEM THAT IS INTENDED TO BE INSTALLED ON THIS |
| STRUCTURE. NOTE MOST OFTHESE SYSTEMS HAVE LOW PRESSURES |
| AND WILL NEED ENHANCED FASTENING IN ZONES 2 & 3. |
| |
| 19) SHEETS 6 & 7 THE TENANT SEPERATION WALL PLEASE |
| INDICATE COMPLIANCE WITH 708.4.1 ROOF CONSTRUCTION. |
| WHEN THE FIRE PARTITION IS CONTINUOUS TO THE UNDERSIDE |
| OF THE ROOF SHEATHING IN OCCUPANCIES OF GROUPS R-1, R-2 |
| AND R-3 AS APPLICABLE IN SECTION 101.2 , IN TYPE III, |
| IV AND V CONSTRUCTION THE FOLLOWING SHALL BE PROVIDED: |
| |
| |
| 708.4.1.1 ROOF SHEATHING. |
| THE ROOF SHEATHING OR DECK SHALL BE OF APPROVED |
| NONCOMBUSTIBLE MATERIALS OR OF FIRE-RETARDANT-TREATED |
| WOOD, FOR A DISTANCE OF 4 FEET (1220 MM); OR |
| |
| 708.4.1.2 ROOF PROTECTION. |
| THE ROOF SHALL BE PROTECTED WITH 0.625-INCH (15.88 MM) |
| TYPE X GYPSUM BOARD DIRECTLY BENEATH THE UNDERSIDE OF |
| THE ROOF SHEATHING OR DECK AND SUPPORTED BY A MINIMUM |
| OF NOMINAL 2-INCH (51 MM) LEDGERS ATTACHED TO THE SIDES |
| OF THE ROOF FRAMING MEMBERS, FOR A MINIMUM DISTANCE OF |
| 4 FEET (1220 MM). |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |