Plan Review Notes For Permit 08050621 |
Permit Number |
08050621 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-06-02 15:53:01 | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | NEC, 2004 FBC CHAPTER 1AS AMENDED AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER | | 106.1.3.FBC. | | | | 2} 600.6(A) (1) WITHIN SIGHT OF THE SIGN THE | | DISCONNECTING MEANS SHALL BE WITHIN SIGHT OF THE SIGN | | OR OUTLINE LIGHTING SYSTEM THAT IT CONTROLS. WHERE THE | | DISCONNECTING MEANS IS OUT OF THE LINE OF SIGHT FROM | | ANY SECTION THAT IS ABLE TO BE ENERGIZED, THE | | DISCONNECTING MEANS SHALL BE CAPABLE OF BEING LOCKED IN | | THE OPEN POSITION.INDICATE SAME ON THE PLANS. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|