Plan Review Notes
Plan Review Notes For Permit 08050621
Permit Number 08050621
Review Stop E
Sequence Number 1
Notes
Date Text
2008-06-02 15:53:01 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, 2004 FBC CHAPTER 1AS AMENDED AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 2} 600.6(A) (1) WITHIN SIGHT OF THE SIGN THE
 DISCONNECTING MEANS SHALL BE WITHIN SIGHT OF THE SIGN
 OR OUTLINE LIGHTING SYSTEM THAT IT CONTROLS. WHERE THE
 DISCONNECTING MEANS IS OUT OF THE LINE OF SIGHT FROM
 ANY SECTION THAT IS ABLE TO BE ENERGIZED, THE
 DISCONNECTING MEANS SHALL BE CAPABLE OF BEING LOCKED IN
 THE OPEN POSITION.INDICATE SAME ON THE PLANS.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718