Plan Review Notes For Permit 08050605 |
Permit Number |
08050605 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-07-16 10:34:29 | ** DENIEDREVIEW ** | | | | | | 1) NOTE:PLEASE SEE THE NEW ELECTRICAL PLAN PROVIDED | | ON 8 1/2 BY 11 DOES NOT CORRELATE WITH PLANS. FOR | | EXAMPLE: PLEASE SEE PLANS WHICH ARE DONE BY THE | | ENGINEER REQUIRES A NEW 50AMP FEED FOR THE NEW AQUA | | LOGIC PANEL YET THE SEPARATE PLAN SUBMITTED INDICATES A | | NEW 30AMP FEED. 240.4, 310.16, 408.4 ETC, FBC 106.1.1 | | FOR CLARITY AND COORDINATION OF PLANS. | | PLEASE SEE THE ENGINEERED PLANS ARE MISSING AN | | EQUIPMENT GROUNDING CONDUCTOR TO THE NEW PANEL.250.122 | | PLEASE SEE ENGINEERS PLANS CALL FOR 3-#8 CONDUCTORS TO | | POOL PUMP IN A 1/2 INCH CONDUIT. PLEASE SEE TABLES IN | | APPENDIX *C* FOR CONDUIT FILL. THIS IS NOT PERMITTED. | | | | PLEASE ADJUST AND COORDINATE PLANS. | | | | | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | |
|