Date |
Text |
2008-05-30 16:12:46 | PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. SHEET 2, PIPING SCHEMATIC: CLEARLY INDICATE THE |
| "AQUA LOGIC W/SALT CHLORINATOR" LOCATION ON THE PIPING |
| SCHEMATIC. PER (W.P.B. AS AMENDED) SECTION 106.1.1 |
| INFORMATION ON CONTRUCTION DOCUMENTS. |
| |
| 2.SHEET 2: PLEASE CORRELATE AND CLEARLY INDICATE THE |
| VENT PIPE SIZE AS BEING 1-1/2" ON THE MAIN DRAIN DETAIL |
| AND PIPING SCHEMATIC AS IT IS BEING INDICATED AS SUCH |
| IN THE "ATMOSPHERIC VENT DETAIL". PER (W.P.B. AS |
| AMENDED) SECTION 106.1.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 3. CLEARLY INDICATE WHICH MODEL POOL HEATER IS BEING |
| USED ON THE RESUBMITTED POOL HEATER MANUFACTURE SHEET. |
| NOTE: THERE ARE SIX DIFFERENT MODELS BEING INDICATED ON |
| THIS SUBMITTAL. PER (W.P.B. AS AMENDED) SECTION 106.1.2 |
| ADDITIONAL DATA. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |