Plan Review Notes
Plan Review Notes For Permit 08050605
Permit Number 08050605
Review Stop P
Sequence Number 1
Notes
Date Text
2008-05-30 16:12:46PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET 2, PIPING SCHEMATIC: CLEARLY INDICATE THE
 "AQUA LOGIC W/SALT CHLORINATOR" LOCATION ON THE PIPING
 SCHEMATIC. PER (W.P.B. AS AMENDED) SECTION 106.1.1
 INFORMATION ON CONTRUCTION DOCUMENTS.
  
 2.SHEET 2: PLEASE CORRELATE AND CLEARLY INDICATE THE
 VENT PIPE SIZE AS BEING 1-1/2" ON THE MAIN DRAIN DETAIL
 AND PIPING SCHEMATIC AS IT IS BEING INDICATED AS SUCH
 IN THE "ATMOSPHERIC VENT DETAIL". PER (W.P.B. AS
 AMENDED) SECTION 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 3. CLEARLY INDICATE WHICH MODEL POOL HEATER IS BEING
 USED ON THE RESUBMITTED POOL HEATER MANUFACTURE SHEET.
 NOTE: THERE ARE SIX DIFFERENT MODELS BEING INDICATED ON
 THIS SUBMITTAL. PER (W.P.B. AS AMENDED) SECTION 106.1.2
 ADDITIONAL DATA.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]