Plan Review Notes For Permit 08050602 |
Permit Number |
08050602 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-05-29 10:38:21 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | | | 1.SHEET 8, AN EDGE DISTANCE OF 2 1/2" REQUIRES A | | FACTOR OF .75 APPLIED TO ANCHOR SPACING. | | | | 2.SEE OPENING 7; 3 1/2" SPACING FOR CONCRETE BLOCK, | | TAPCONS, SPAN OVER 8'6" WITH FACTOR APPLIED RESULTS IN | | AN ANCHOR SPACING OF 2.6, MINIMUM OF 3" REQUIRED. | | PLEASE REVISE INSTALLATION SCHEDULE. | | | | 3.SEE OPENINGS 10 AND 11, 9" SPACING FOR CONCRETE | | SUBSTRATE WITH 3" EDGE DISTANCE BUT THE INSTALLATION | | SCHEDULE STATES THIS IS CONCRETE BLOCK, 2 1/2" EDGE | | DISTANCE.PLEASE REVISE THE INSTALLATION SCHEDULE. | | | | 4.COMMENTS MAY APPLY TO OTHER OPENINGS.PLEASE CHECK | | ALL. |
|