Plan Review Notes
Plan Review Notes For Permit 08050602
Permit Number 08050602
Review Stop B
Sequence Number 1
Notes
Date Text
2008-05-29 10:38:21****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.SHEET 8, AN EDGE DISTANCE OF 2 1/2" REQUIRES A
 FACTOR OF .75 APPLIED TO ANCHOR SPACING.
  
 2.SEE OPENING 7; 3 1/2" SPACING FOR CONCRETE BLOCK,
 TAPCONS, SPAN OVER 8'6" WITH FACTOR APPLIED RESULTS IN
 AN ANCHOR SPACING OF 2.6, MINIMUM OF 3" REQUIRED.
 PLEASE REVISE INSTALLATION SCHEDULE.
  
 3.SEE OPENINGS 10 AND 11, 9" SPACING FOR CONCRETE
 SUBSTRATE WITH 3" EDGE DISTANCE BUT THE INSTALLATION
 SCHEDULE STATES THIS IS CONCRETE BLOCK, 2 1/2" EDGE
 DISTANCE.PLEASE REVISE THE INSTALLATION SCHEDULE.
  
 4.COMMENTS MAY APPLY TO OTHER OPENINGS.PLEASE CHECK
 ALL.