2008-10-09 14:21:26BUILDING PROVISO: FBC BUILDING 3110.1.2 / CITY OF WPB
 CODE OF ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED
 IN AN "A" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE MAY
 BE REQUIRED. DEPENDING ON THE TIMING OF THE BUILDING
 C.O. IF THE GENERATORS ARE GOING TO RECEIVE THEIR CO AT
 THE SAME TIME AS THE BUILDING A FLOOD ZONE CERTIFICATE
 WILL BE REQUIRED. IF THE GENERATORS ARE GOING TO BE
 FINAL AFTER THE BUILDING C.O. THEN EITHER A SURVEY WITH
 ELEVATION HEIGHT OR DESIGNER OF RECORD PROVIDING SITE
 PLAN WITH ASSOCIATED SLAB ELEVATION. THE MINIMUM FLOOD
 ELEVATION THE SLAB MAY BE SET AT IS 13'-6" IN A "A-9"
 FLOOD ZONE, THIS MAY BE ACCOMPLISHED AT TIME OF THE
 FINAL.