Plan Review Notes
Plan Review Notes For Permit 08050578
Permit Number 08050578
Review Stop FUEL
Sequence Number 2
Notes
Date Text
2008-08-11 11:46:16PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLANS PAGE E5.1 GENERATOR SPECIFICATIONS LINE #4
 STATES THE FUEL TANK IS 500 GALLONS, THE SUBMITTAL
 STATES THE FUEL TANK IS 1,330 GALLONS. THE TWO MUST
 COINSIDE, PLEASE CORRECT.
  
 2) AS NOTED IN LAST REVIEW 6-23-08 (MECH.). SHOW ON
 PLAN SP-1, TYPE OF FUEL, FUEL TANK CAPACITY, AND
 LOCATION OF FUEL STORAGE TANK FOR GENERATOR, PER NFPA
 30 4.3.2.1.
  
 3) AFTER CORRECTING PLANS THEY NEED TO BE SUBMITTED TO
 PALM BEACH COUNTY DEPT. OF ENVIRONMENTAL RESOURCES
 MANAGEMENT (D.E.R.M.) FOR REVIEW AND STAMPING, YOU MAY
 CALL (561) 233-2400 FOR MORE INFORMATION. THEN SUBMIT
 TO CITY OF W.P.B. BUILDING DEPT..
  
 FUEL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]