Plan Review Notes For Permit 08050578 |
Permit Number |
08050578 |
|
Review Stop |
FUEL |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-08-11 11:46:16 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) PLANS PAGE E5.1 GENERATOR SPECIFICATIONS LINE #4 | | STATES THE FUEL TANK IS 500 GALLONS, THE SUBMITTAL | | STATES THE FUEL TANK IS 1,330 GALLONS. THE TWO MUST | | COINSIDE, PLEASE CORRECT. | | | | 2) AS NOTED IN LAST REVIEW 6-23-08 (MECH.). SHOW ON | | PLAN SP-1, TYPE OF FUEL, FUEL TANK CAPACITY, AND | | LOCATION OF FUEL STORAGE TANK FOR GENERATOR, PER NFPA | | 30 4.3.2.1. | | | | 3) AFTER CORRECTING PLANS THEY NEED TO BE SUBMITTED TO | | PALM BEACH COUNTY DEPT. OF ENVIRONMENTAL RESOURCES | | MANAGEMENT (D.E.R.M.) FOR REVIEW AND STAMPING, YOU MAY | | CALL (561) 233-2400 FOR MORE INFORMATION. THEN SUBMIT | | TO CITY OF W.P.B. BUILDING DEPT.. | | | | FUEL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|