Notes |
Date |
Text |
2008-08-21 14:22:33 | ***DENIED*** | | | | 1) RESPONSE LETTER REFERS TO REVISED SHEET E0.1. NO | | CODE REFERENCE FOUND. ADD NFPA 110, STANDARD FOR | | EMERGENCY POWER AND STANDBY SYSTEMS TO LIST OF CODES | | AND STANDARDS ON SHEET E0.1. | | | | 2) CLEARLY IDENTIFY THE FUEL TYPE AND SHOW LOCATION OF | | FUEL SOURCE. RESPONSE LETTER REFERS TO THE FLOOR PLAN | | ON SHEET SP-1. | | | | 3) PLEASE NOTE THAT THIS WRITER CANNOT DETERMINE | | BUILDING OPENINGS WITH REGARD TO EXHAUST TERMINUS ON | | FLOOR PLAN. IF NOT APPLICABLE, PLEASE ADVISE RELATIVE | | TO THE FUEL TYPE. | | | | 4) KAMM CONSULTING SUBMITTED A LETTER THAT DOES NOT | | ADDRESS WHAT BUILDING LIFE SAFETY EQUIPMENT IS TIED TO | | THE GENERATOR. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|