Plan Review Notes
Plan Review Notes For Permit 08050578
Permit Number 08050578
Review Stop E
Sequence Number 2
Notes
Date Text
2008-08-12 15:08:29 
 ** PLANS ARE COMING BACK FOR OTHER CORRECTIONS.
  
  
 1) NOTE: PLANS/RISER NEED TO BE LABELED WITH ALL NEW
 SIGNAGE FOR DISCONNECTING MEANS OF NORMAL AND EMERGENCY
 POWER. THIS IS BASED ON THE FACT THERE ARE AT LEAST 6
 MEANS OF DISCONNECT TO SHUT POWER OFF TO BUILDING AT
 THIS TIME.
 230.2E, 702.8
  
 2) NOTE: PLANS CALL FOR A SEPARATELY DERIVED GENERATOR
 YET THE SPECS/MANUFACTURES CUT SHEETS/ BILL OF
 MATERIALS INDICATES TRANSFER SWITCH AS 3-POLE. IT WAS
 NOTED BY ENGINEER OF RECORD HOWEVER NO NEW SPECS WERE
 SUBMITTED.
 PLEASE SEE SHEET IN REAR OF SUBMITTAL PACKAGE WHICH
 STATES THE ISOLATORS ARE N/A. (NOT APPLICABLE). PLEASE
 SEE NFPA-110 CHAPTER 7.
  
 3) NOTE: PLEASE SEE E.01 AS THE 2002 NFPA-70 (NEC) IS
 QUOTED. THIS CAN BE REDLINED WITHOUT CHANGING SHEET.
 2005 NFPA-70.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]