2008-08-12 15:08:29 | |
| ** PLANS ARE COMING BACK FOR OTHER CORRECTIONS. |
| |
| |
| 1) NOTE: PLANS/RISER NEED TO BE LABELED WITH ALL NEW |
| SIGNAGE FOR DISCONNECTING MEANS OF NORMAL AND EMERGENCY |
| POWER. THIS IS BASED ON THE FACT THERE ARE AT LEAST 6 |
| MEANS OF DISCONNECT TO SHUT POWER OFF TO BUILDING AT |
| THIS TIME. |
| 230.2E, 702.8 |
| |
| 2) NOTE: PLANS CALL FOR A SEPARATELY DERIVED GENERATOR |
| YET THE SPECS/MANUFACTURES CUT SHEETS/ BILL OF |
| MATERIALS INDICATES TRANSFER SWITCH AS 3-POLE. IT WAS |
| NOTED BY ENGINEER OF RECORD HOWEVER NO NEW SPECS WERE |
| SUBMITTED. |
| PLEASE SEE SHEET IN REAR OF SUBMITTAL PACKAGE WHICH |
| STATES THE ISOLATORS ARE N/A. (NOT APPLICABLE). PLEASE |
| SEE NFPA-110 CHAPTER 7. |
| |
| 3) NOTE: PLEASE SEE E.01 AS THE 2002 NFPA-70 (NEC) IS |
| QUOTED. THIS CAN BE REDLINED WITHOUT CHANGING SHEET. |
| 2005 NFPA-70. |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |