2008-08-12 07:45:53BUILDING PLAN REVIEW
 PERMIT: 08050578
 ADD: 1641 WORTHINGTON RD
 CONT: HEDRICK BROTHERS
 TEL: (561)662-0785
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 08-12-08
 2ND REVIEW
 ACTION: DENIED
 (2) 500 KW GENERATORS
 1) COMPLIED.
  
 2) NOTE, BUILDING PROVISO: FBC BUILDING 3110.1.2 / CITY
 OF WPB CODE OF ORDINANCES SECTION 94-546. STRUCTURE IS
 LOCATED IN AN "A" FLOOD ZONE. A FLOOD ELEVATION
 CERTIFICATE MAY BE REQUIRED. DEPENDING ON THE TIMING OF
 THE BUILDING C.O. IF THE GENERATORS ARE GOING TO BE
 CO'ED AT THE SAME TIME AS THE BUILDING A FLOOD ZONE
 CERTIFICATE WILL BE REQUIRED. IF THE GENERATORS ARE
 GOING TO BE FINALED AFTER THE BUILDING C.O. THEN EITHER
 A SURVEY WITH ELEVATION HEIGTH OR DESIGNER OF RECORD
 PROVIDING SITE PLAN WITH ASSCIATED SLAB ELEVATION. THE
 MINIMUM FLOOD ELEVATION THE SLAB MAY BE SET AT IS
 13'-6" IN A "A-9" FLOOD ZONE, THIS MAY BE ACCOMPLISHED
 AT TIME OF THE FINAL.
  
 3) 2ND REQUEST, THERE ARE NO ARCHITECTURAL OR
 STRUCTURAL PLANS INDICATING THE SIZE OF ANCHOR FROM THE
 EQUIPMENT PAD TO THE GENERATOR FRAME TO RESIST THE
 MOMENT OF OVERTURNING. 1609. 1.3, ANCHORAGE AGAINST
 MOMENT OF OVERTURNING, UPLIFT AND SLIDING. RESPONSE
 INDICATES SEE NOTES ON SP-1, NO NOTES FOR ANCHORING OF
 UNITS.
  
 4) COMPLIED.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved