2008-06-10 12:13:23 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) PLEASE SUBMIT A SITE PLAN SHOWING THE PROPERTY | | LINES, BUILDINGS, AND GENERATOR LOCATION, PER NFPA 37 | | 4.1.4. | | | | 2) PLEASE SUBMIT DETAILED MANUFACTURER'S | | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE | | GENERATOR. | | | | 3) PLEASE STATE ON PLANS WHAT FUEL TYPE THE GENERATOR | | IS. | | | | 4) IF FUEL TYPE IS OTHER THAN NATURAL GAS SHOW THE | | LOCATION OF THE FUEL STORAGE TANK AND CAPACITY ON THE | | SITE PLAN, SEE NFPA 317.9. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|